07
SZ-81145
Sr.No.
Description of parameters and functions.
Parameter setting
method.
Parameter
EP
Function : To end programming.
15
Once the SET key is pressed the control
goes into the normal mode and displays
the temperature.
To end Program mode press
set key.
FS
Function : To restore all factory set values.
14
To change the parameter value,
press set key.
Use UP/DOWN keys to set desired
range.
Range
Min
Max
Fact. Set
0
1
0
To restore default settings of the
controller. When set to 1, all parameters
are programmed to factory settings. Used
to debug setting related problems.
Ht
Lt
Fault Messages :
Message
Parameter
Description
High temperature alarm for Room. Means room
temperature is above the set value.
Low temperature alarm for Room. Means room
temperature is below the set value.
PP
Room probe Fail means Temperature / RH
sensor not connected or out of range .
HH
LH
High humidity alarm for Room. Means room
humidity is above the set value.
Low humidity alarm for Room. Means room
humidity is below the set value.
P2, P4
P3, P4
H2, H4
H3, H4
08
SZ-81145
Technical Data