Name
Values (Range)
Unit
Step
Default
Description
Characterist3
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 3
IN3>
1 - 2500
%IB
1
33
Residual current operate level for step 3
in % of IBase
t3
0.000 - 60.000
s
0.001
0.800
Def time delay or add time delay for
inverse char of step 3
k3
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 3 selected
time characteristic
IMin3
1.00 - 10000.00
%IB
1.00
33
Minimum operate residual current for
step 3 in % of IBase
t3Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 3
IN3Mult
1.0 - 10.0
-
0.1
2.0
Multiplier for the residual current setting
value for step 3
HarmBlock3
Off
On
-
-
On
Enable block of step 3 from harmonic
restrain
DirMode4
Off
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 4 (Off, Non-dir,
Forward, Reverse)
Characterist4
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 4
IN4>
1 - 2500
%IB
1
17
Residual current operate level for step 4
in % of IBase
Table continues on next page
1MRK 505 384-UEN A
Section 6
Current protection
Breaker protection REQ650 2.2 IEC
109
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...