PID-6799-OUTPUTSIGNALS v2
Table 170:
SXCBR Output signals
Name
Type
Description
XPOS
GROUP SIGNAL
Group connection to CSWI for XCBR and XSWI
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OP_BLKD
BOOLEAN
Indication that the function is blocked for open
commands
CL_BLKD
BOOLEAN
Indication that the function is blocked for close
commands
UPD_BLKD
BOOLEAN
Update of position indication is blocked
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
TR_POS
INTEGER
Truck position indication
CNT_VAL
INTEGER
Operation counter value
L_CAUSE
INTEGER
Latest value of the error indication during
command
EEHEALTH
INTEGER
External equipment health. 1=No warning or
alarm, 2=Warning, 3=Alarm
CBOPCAP
INTEGER
Breaker operating capability 1 = None, 2 = O, 3 =
CO, 4 = OCO, 5 = COCO, 6+ = More
9.4.7.4
Settings
PID-6799-SETTINGS v2
Table 171:
SXCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tStartMove
0.000 - 60.000
s
0.001
0.100
Supervision time for the apparatus to
move after a command
tIntermediate
0.000 - 60.000
s
0.001
0.150
Allowed time for intermediate position
AdaptivePulse
Not adaptive
Adaptive
-
-
Not adaptive
Output resets when a new correct end
position is reached
tOpenPulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for open command
tClosePulse
0.000 - 60.000
s
0.001
0.200
Output pulse length for close command
InitialCount
0 - 20000
-
1
0
Initial number of operations (Initial count
value)
9.4.7.5
Operation principle
M13487-4 v7
The circuit breaker function (SXCBR) is used by other functions such as, for
example, switch controller, protection functions, autorecloser function or an IEC
61850 client residing in another IED or the operator place. This switch function
executes commands, evaluates block conditions and evaluates different time
supervision conditions. Only if all conditions indicate a switch operation to be
Section 9
1MRK 505 384-UEN A
Control
292
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...