PID-6836-OUTPUTSIGNALS v2
Table 277:
TEIGAPC Output signals
Name
Type
Description
WARNING
BOOLEAN
Indicator of the integrated time has reached the
warning limit
ALARM
BOOLEAN
Indicator of the integrated time has reached the
alarm limit
OVERFLOW
BOOLEAN
Indicator of the integrated time has reached the
overflow limit
ACCTIME
REAL
Integrated elapsed time in seconds
10.13.5
Settings
PID-6836-SETTINGS v2
Table 278:
TEIGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
tWarning
1.00 - 999999.00
s
0.01
600.00
Time limit for warning supervision
tAlarm
1.00 - 999999.00
s
0.01
1200.00
Time limit for alarm supervision
10.13.6
Operation principle
GUID-04CC8365-DCDE-4DC7-BEF0-6EF8382305DD v3
The elapsed time integrator (TEIGAPC) provides
•
time integration, accumulating the elapsed time when a given binary signal has
been high
•
blocking and reset of the total integrated time
•
supervision of limit transgression and overflow, the overflow limit is fixed to
999999.9 seconds
•
retaining of the integrated value
Figure
describes the simplified logic of the function where the block “Time
Integration“ covers the logics for the first two items listed above while the block
“Transgression Supervision Plus Retain“ contains the logics for the last two.
1MRK 505 384-UEN A
Section 10
Logic
Breaker protection REQ650 2.2 IEC
381
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...