GUID-47094054-A828-459B-BE6A-D7FA1B317DA7 v6
Table 324:
VMSQItechnical data
Function
Range or value
Accuracy
Voltage positive sequence, U1
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage zero sequence, 3U0
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage negative sequence, U2
(10 to 300) V
±
0.5% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.5 degrees at U ≤ 50 V
±
0.2 degrees at U > 50 V
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6
Table 325:
VNMMXU technical data
Function
Range or value
Accuracy
Voltage
(5 to 175) V
±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle
(5 to 175) V
±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
11.2
Gas medium supervision SSIMG
GUID-358AD8F8-AE06-4AEA-9969-46E5299D5B4B v3
11.2.1
Identification
GUID-AD96C26E-C3E5-4B21-9ED6-12E540954AC3 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation gas monitoring function
SSIMG
-
63
11.2.2
Functionality
GUID-0692CD0D-F33E-4370-AC91-B216CAAAFC28 v6
Insulation supervision for gas medium (SSIMG) is used for monitoring the circuit
breaker condition. Binary information based on the gas pressure in the circuit
breaker is used as input signals to the function. In addition, the function generates
alarms based on received information.
Section 11
1MRK 505 384-UEN A
Monitoring
426
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...