Name
Values (Range)
Unit
Step
Default
Description
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog channel 3
in % of signal
OverTrigOp03
Off
On
-
-
Off
Use over level trigger for analog channel
3 (on) or not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog channel 3 in
% of signal
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Off
On
-
-
Off
Use under level trigger for analog
channel 4 (on) or not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog channel 4
in % of signal
OverTrigOp04
Off
On
-
-
Off
Use over level trigger for analog channel
4 (on) or not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog channel 4 in
% of signal
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Off
On
-
-
Off
Use under level trigger for analog
channel 5 (on) or not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog channel 5
in % of signal
OverTrigOp05
Off
On
-
-
Off
Use over level trigger for analog channel
5 (on) or not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog channel 5 in
% of signal
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Off
On
-
-
Off
Use under level trigger for analog
channel 6 (on) or not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog channel 6
in % of signal
OverTrigOp06
Off
On
-
-
Off
Use over level trigger for analog channel
6 (on) or not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog channel 6 in
% of signal
NomValue07
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 7
UnderTrigOp07
Off
On
-
-
Off
Use under level trigger for analog
channel 7 (on) or not (off)
UnderTrigLe07
0 - 200
%
1
50
Under trigger level for analog channel 7
in % of signal
OverTrigOp07
Off
On
-
-
Off
Use over level trigger for analog channel
7 (on) or not (off)
OverTrigLe07
0 - 5000
%
1
200
Over trigger level for analog channel 7 in
% of signal
NomValue08
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 8
UnderTrigOp08
Off
On
-
-
Off
Use under level trigger for analog
channel 8 (on) or not (off)
UnderTrigLe08
0 - 200
%
1
50
Under trigger level for analog channel 8
in % of signal
Table continues on next page
1MRK 505 384-UEN A
Section 11
Monitoring
Breaker protection REQ650 2.2 IEC
459
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...