Data Value
Data Valid
Comm Valid
Test
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
Freeze
0
0
0
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (if
easy GOOSE engineering is enabled) to receive the integer values.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
14.4.8
GOOSE function block to receive a measurand value
GOOSEMVRCV
14.4.8.1
Identification
GUID-B1FFBE08-C823-4A58-9FE0-A9A20DA6BB44 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV
-
-
14.4.8.2
Functionality
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v3
GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via
GOOSE.
14.4.8.3
Function block
GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1
IEC10000251-2-en.vsd
GOOSEMVRCV
BLOCK
^SRCMVOUT
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V2 EN-US
Figure 256:
GOOSEMVRCV function block
Section 14
1MRK 505 384-UEN A
Station communication
532
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...