Data Value
Data Valid
Comm Valid
Test
Incoming data with q=Normal
Updated
1
1
0
Incoming data with q=oldData
Freeze
0
1
0
Incoming data with q=Invalid
Freeze
0
1
0
Incoming data with q=test
Freeze
0
1
1
Incoming data with q=test+oldData
Freeze
0
1
1
Receiver in block
Freeze
0
1
0
Receiver in block and communication
error
Freeze
0
0
0
Receiver in test mode and incoming
data with q= Normal
Updated
1
1
0
Receiver in test mode and incoming
data with q= Test
Updated
1
1
1
Communication Error
Freeze
0
0
0
The input of this GOOSE block must be linked either in SMT by
means of a cross or in ACT by means of a GOOSE connection (in
case easy GOOSE engineering is enabled) to receive the measured
value.
The implementation for IEC 61850 quality data handling is
restricted to a simple level. If quality data validity is GOOD then
the DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
14.4.9
GOOSE function block to receive a single point value
GOOSESPRCV
14.4.9.1
Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV
-
-
14.4.9.2
Functionality
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v3
GOOSESPRCV is used to receive a single point value using IEC 61850 protocol
via GOOSE.
Section 14
1MRK 505 384-UEN A
Station communication
534
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...