14.8.5
Function status earth-fault for IEC 60870-5-103 I103EF
GUID-F23B392E-B55D-4BC3-A0A6-B7992D551092 v1
14.8.5.1
Functionality
GUID-13F90E95-7C8C-4DCB-A9D8-2489B66DB81A v2
I103EF is a function block with defined functions for earth fault indications in
monitor direction. This block includes the
FunctionType
parameter, and the
information number parameter is defined for each output signal.
14.8.5.2
Identification
GUID-033731B7-1B71-4CCC-8356-1C03CBCB23FA v1
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status earth-fault for IEC
60870-5-103
I103EF
-
-
14.8.5.3
Function block
GUID-25B47484-2976-4063-BD81-AE02D03B08B0 v1
IEC10000290-1-en.vsd
I103EF
BLOCK
51_EFFW
52_EFREV
IEC10000290 V1 EN-US
Figure 274:
I103EF function block
14.8.5.4
Signals
PID-3974-INPUTSIGNALS v5
Table 442:
I103EF Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
51_EFFW
BOOLEAN
0
Information number 51, earth-fault forward
52_EFREV
BOOLEAN
0
Information number 52, earth-fault reverse
14.8.5.5
Settings
PID-3974-SETTINGS v5
Table 443:
I103EF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
160
Function type (1-255)
Section 14
1MRK 505 384-UEN A
Station communication
592
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...