4.1.3.1
Setting parameters for binary input modules
PID-3473-SETTINGS v2
Table 18:
BIM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation Off/On
DebounceTime
0.001 - 0.020
s
0.001
0.001
Debounce time for binary inputs
OscBlock
1 - 40
Hz
1
40
Oscillation block limit
OscRelease
1 - 30
Hz
1
30
Oscillation release limit
4.1.3.2
Setting parameters for binary input/output module
PID-4050-SETTINGS v2
Table 19:
IOMIN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Binary input/output module in operation
(On) or not (Off)
DebounceTime
0.001 - 0.020
s
0.001
0.001
Debounce time for binary inputs
OscBlock
1 - 40
Hz
1
40
Oscillation block limit
OscRelease
1 - 30
Hz
1
30
Oscillation release limit
Section 4
1MRK 505 384-UEN A
Binary input and output modules
56