I/O events are time stamped locally on each module for minimum time deviance
and stored by the event recorder if present.
SEMOD175370-4 v1
The binary input/output module version with MOV protected contacts can for
example be used in applications where breaking high inductive load would cause
excessive wear of the contacts.
The test voltage across open contact is lower for this version of the
binary input/output module.
xx04000069.vsd
IEC04000069 V1 EN-US
Figure 313:
IOM with MOV protection, relay example
17.2.9.3
Signals
PID-6434-OUTPUTSIGNALS v4
Table 556:
IOMIN Output signals
Name
Type
Description
STATUS
BOOLEAN
Binary input part of IOM module status
BI1
BOOLEAN
Binary input 1 value
BI2
BOOLEAN
Binary input 2 value
BI3
BOOLEAN
Binary input 3 value
BI4
BOOLEAN
Binary input 4 value
BI5
BOOLEAN
Binary input 5 value
BI6
BOOLEAN
Binary input 6 value
BI7
BOOLEAN
Binary input 7 value
BI8
BOOLEAN
Binary input 8 value
OSCWRN
BOOLEAN
Oscillation warning
PID-4049-INPUTSIGNALS v2
Table 557:
IOMOUT Input signals
Name
Type
Default
Description
BLKOUT
BOOLEAN
0
Block binary outputs
BO1
BOOLEAN
0
Binary output 1
BO2
BOOLEAN
0
Binary output 2
Table continues on next page
Section 17
1MRK 505 384-UEN A
IED hardware
700
Breaker protection REQ650 2.2 IEC
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...