Function
Range or value
Accuracy
Inverse time characteristics for step 1
and step 2, see table
-
See table
Definite time delay, step 1 at 1.2 x U
set
to
0
(0.00-6000.00) s
±0.2% or ±40ms
whichever is greater
Definite time delay, step 2 at 1.2 x U
set
to
0
(0.000-60.000) s
±0.2% or ±40ms
whichever is greater
Minimum operate time, inverse
characteristics
(0.000–60.000) s
±0.5% or ±40ms
whichever is greater
Operate time, start at 2 x U
set
to 0
Min. = 15 ms
Max. = 30 ms
-
Reset time, start at 0 to 2 x U
set
Min. = 15 ms
Max. = 30 ms
-
Operate time, start at 1.2 x U
set
to 0
Min. = 5 ms
Max. = 25 ms
-
Reset time, start at 0 to 1.2 x U
set
Min. = 15 ms
Max. = 35 ms
-
Critical impulse time
5 ms typically at 1.2 x U
set
to 0
-
Impulse margin time
15 ms typically
-
7.2
Two step overvoltage protection OV2PTOV
IP14545-1 v3
7.2.1
Identification
M17002-1 v8
Function description
IEC 61850
identification
IEC 60617 identification
ANSI/IEEE C37.2
device number
Two step overvoltage protection
OV2PTOV
3U>
SYMBOL-C-2U-SMALLER-THAN V2 EN-US
59
7.2.2
Functionality OV2PTOV
M13798-3 v15
Overvoltages may occur in the power system during abnormal conditions such as
sudden power loss, tap changer regulating failures, and open line ends on long
lines.
OV2PTOV has two voltage steps, each of them with inverse or definite time
delayed.
OV2PTOV has a high reset ratio to allow settings close to system service voltage.
1MRK 505 384-UEN A
Section 7
Voltage protection
Breaker protection REQ650 2.2 IEC
177
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...