9.4.4.5
Operation principle
M13446-4 v7
The function sends information about the Permitted Source To Operate (PSTO) and
blocking conditions to other functions within the bay for example, switch control
functions and voltage control functions. The functionality of the Bay control
(QCBAY) function is mainly described by the LLN0 node in the IEC 61850-8-1
edition 2 standard, applied to one bay. In IEC 61850 edition 1 the functionality is
not described by the LLN0 node or any other node, therefore the Bay control
function is represented as a vendor specific node in edition 1.
Local panel switch
M13446-7 v7
The local panel switch is a switch that defines the operator place selection. The
switch connected to this function can have three positions (remote/local/off). The
positions are here defined so that remote means that operation is allowed from
station and/or remote level and local means that operation is allowed from the IED
level. The local/remote switch is also on the control/protection IED itself, which
means that the position of the switch and its validity information are connected
internally, not via I/O boards. When the switch is mounted separately from the IED
the signals are connected to the function via I/O boards.
When the local panel switch (or LHMI selection, depending on the set source to
select this) is in Off position, all commands from remote and local level will be
ignored. If the position for the local/remote switch is not valid the PSTO output
will always be set to faulty state (3), which means no possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch,
the function blocks LOCREM and LOCREMCTRL are needed and connected to
QCBAY.
Permitted Source To Operate (PSTO)
M13446-16 v9
The actual state of the operator place is presented by the value of the Permitted
Source To Operate, PSTO signal. The PSTO value is evaluated from the local/
remote switch position according to Table
. In addition, there are two settings
and one command that affect the value of the PSTO signal.
If the setting
AllPSTOValid
is set to
No Priority
and the LR-switch position is in
Local or Remote state, the PSTO output is set to 5 (all), that is, it is permitted to
operate from local, station and remote level without any priority. When the external
panel switch is in Off position, the PSTO output shows the actual state of the
switch that is, 0. In this case, it is not possible to control anything. The LocSta
command value is forced to
FALSE
if
AllPSTOValid
is set to
No priority
.
If the setting
RemoteIncStation
is set to
Yes
and the LR-switch position is in
Remote state, the PSTO output is set to 2 (Station or Remote), that is, it is
permitted to operate from both station and remote level without any priority.
If the LR-switch position is in Remote state, and
AllPSTOValid
is set to
Priority
and
RemoteIncStation
is set to
No
, the switching between station and remote level
control is done through the command LocSta. The command is accessible only
through the IEC 61850 Edition 2 protocol.
1MRK 505 384-UEN A
Section 9
Control
Breaker protection REQ650 2.2 IEC
275
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...