17.2.2.3
Technical data
SEMOD55319-1 v1
SEMOD55310-2 v11
Table 541:
SFP - Optical ethernet port
Quantity
Rated value
Number of channels
4 single or 2 redundant can be used for single or
redundant communication using any protocol
Standard
IEEE 802.3u 100BASE-FX
Type of fiber
62.5/125
m
m multimode fibre
Wave length
1310 nm, Class 1 laser safety
Optical connector
Type LC
Communication speed
Fast Ethernet 100 Mbit/s
Table 542:
SFP - Galvanic RJ45
Quantity
Rated value
Number of
channels
Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Standard
IEEE 802.3u 100BASE-TX
Type of cable
Cat5e FTP
Connector
Type RJ45
Communication
Speed
Fast Ethernet 100 Mbit/s
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v2
Table 543:
NUM: Communication ports
NUM
4 Ethernet ports
1 Basic, 3 Optional
Ethernet connection type
SFP Optical LC or Galvanic RJ45
17.2.3
Power supply module (PSM)
IP15594-1 v1
17.2.3.1
Introduction
M11595-3 v6
The power supply module is used to provide the correct internal voltages and full
isolation between the IED and the battery system. An internal fail alarm output is
available.
Alternative connectors of Ring lug or Compression type can be ordered.
17.2.3.2
Design
IP14278-1 v1
M6377-3 v2
There are two types of the power supply module. They are designed for different
DC input voltage ranges see table
. The power supply module contains a built-
1MRK 505 384-UEN A
Section 17
IED hardware
Breaker protection REQ650 2.2 IEC
681
Technical manual
Summary of Contents for impreza 2017
Page 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Page 2: ......
Page 32: ...26...
Page 42: ...36...
Page 50: ...44...
Page 168: ...162...
Page 226: ...220...
Page 396: ...390...
Page 498: ...492...
Page 512: ...506...
Page 528: ...522...
Page 632: ...626...
Page 650: ...644...
Page 738: ...732...
Page 784: ...778...
Page 785: ...779...