EES USER MANUAL
SECTION 2
12
2.3
FUNCTIONAL DESCRIPTION
—MIXED AIR
TEMPERATURE SENSOR
. The mixed air temperature
sensor is mounted in the compressor enclosure in
front of the combination cooler. This sensor monitors
the temperature of the mixture of bypass and outdoor
air. Based on this sensor, the proportional controller
(
) will modulate the incoming and bypass
air damper actuator motors to maintain a set
temperature of air into the cooler.
2.4
FUNCTIONAL DESCRIPTION
—OUTSIDE AIR
TEMPERATURE SENSOR
. The outdoor air temperature
sensor is mounted in the incoming air stream outside
of the compressor enclosure. This sensor monitors
the temperature of the incoming air. When the
temperature of the incoming air exceeds the set
value on the outside air temperature controller
(
), all heat of compression is rejected
outdoors. In addition, the incoming air damper is
fully opened and the bypass air damper fully closed.
Outside Air
Sensor
Incoming Air
Damper
Recovered
Air Damper
Rejected Air
Damper
Access Panel
Bypass Air Damper
and Actuator
Mixed Air Sensor
EES Control
Enclosure
Incoming Air
Damper and
Actuator
Rejected
Air Damper
and Actuator
Recovered
Air Damper
and Actuator
Figure 2-1: Sullair Integral Heat Recovery System
Summary of Contents for 3000 EES
Page 10: ...NOTES 10 ...
Page 16: ...16 BLANK PAGE ...
Page 20: ...EES USER MANUAL SECTION 3 20 Figure 3 1 Identification EES 02250175 281 R00 ...
Page 21: ...SECTION 3 EES USER MANUAL 21 Figure 3 2 Wiring Diagram EES 02250175 264 R01 ...
Page 22: ...22 BLANK PAGE ...
Page 28: ...28 BLANK PAGE ...
Page 36: ...36 BLANK PAGE ...
Page 38: ...38 BLANK PAGE ...
Page 44: ...44 BLANK PAGE ...
Page 45: ...Section 8 45 EES USER MANUAL PARTS LISTS ...
Page 46: ...EES USER MANUAL SECTION 8 46 8 1 EES ENCLOSURE ASSEMBLY 02250175 279 R00 ...
Page 48: ...EES USER MANUAL SECTION 8 48 8 2 EES ELECTRICAL CONTROL ASSEMBLY 02250171 648 R00 ...
Page 50: ...EES USER MANUAL SECTION 8 50 8 3 EES DISCHARGE ENCLOSURE ASSEMBLY 02250171 646 R00 ...
Page 52: ...EES USER MANUAL SECTION 8 52 8 4 EES PACKAGE CLEAN AIR INLET OPTION 02250176 044 R00 ...
Page 54: ...54 BLANK PAGE ...
Page 55: ...NOTES 55 ...