CONTROL PANEL SULZER APC 1/2B 

 USER GUIDE 

Rev.13  (2018/08/30) 

 

 
TEMPERATURE ELECTRODES IN PUMP FOR MONITORING 

Some pumps have thermal sensors in areas with higher warming trend, as the motor winding and the 
upper and lower bearings. As standard the APC box 1/2B is ready to receive a temperature signal for 
pump  bimetal  type  (in  case  of  PTC  or  PT100  should  add  a  module  temperature  monitoring  CA442 

optional).  For  adequate  protection  and  monitoring,  these  sensors  must  be  properly  connected  to  the 
box. If pump heating thermistor is activated bimetallic APC box stops the pump instant both manually, 
or semi-automatic through the control line of the picture; alarm indicating the PC 242 via the text alarm 

"High temperature pump Bn" and is marked by floating contact general fault, plus alternating activated 
PC 242 from pump failure launching the next bomb touched by alternating cycle. Any APC considers 
that  after  a  pump  stop  alarm  temperature  sensor,  usually  the  pump  will  cool  faster  because  it  has 

stopped  and  is  submerged,  so  keep  it  locked  up  driver  alarm  reset,  after  which  the  reenters  pump 
service. 

Be sure to connect the terminals shorted box for connection of the temperature sensor 

for each pump or auxiliary equipment that does not have such a signal, otherwise controller will 

never start the pump. 

 

 

MCB AND EARTH PROTECTION SWITCH FOR EACH POWER OUTPUT TO PUMP  

 
A  picture  APC  protects  each  motor  output  through  a  curved  magnetic  protection  switch  motor  (with 

adjustable  sensitivity  thermal  trip)  and  a  differential  protection  switch  for industrial  (300mA  sensitivity 
and instantaneous trip). 
Instead  of  using  general  differential  protection frame header,  used  motor  output  protection  to  ensure 

the availability of pumps in pumping, since in case of tripping earth leakage current in a pump or the 
feed  cable,  or  against  nuisance  tripping  on  start,  would  act  only  protecting the  pump leaving the  rest 
available (thus differential protection is especially important in pumping rainwater). 

Fully finished in APCs, is connected to a digital input signal PC 242 combined for each set of magneto-
differential switches so that in case of fire, the controller instructed with the text "pump motor Prot Bn 
Shot" and signalled by potential free contact general fault. From the alarm was raised, the pump is de-

energized it, stop giving PC 242 running order and cut his line of command in the box, but not locked, 
so  that  once  manually  reset  the  pump  protection  come  back  into  service  even if  not  reset  the  alarm, 
should  be  so  has  acted  on  the  protection  manually,  plus  alternating  activated  PC  242  from  pump 

failure. 

 

 

MOTOR CURRENT CONSUMPTION  

We  monitor  motor  current  consumption  of  each  pump  in  an  APC  Fully  finished  using  a  current 
transformer as special (with type 4-20mA output) per pump connected to the PC for 242 analogue input 

(or signal control equipment when motor soft starters or variable frequency). This allows us to generate 
alarms  for  both  high  consumption  value  as  reduced  respectively  marked  as  "High  consumption  Bn 
pump" and "Reduced consumption Bn bomb" on the display of PC 242, and in both cases by floating 

contact failure overall picture. This alarm does not cause stopping of the pump, so it can be used as a 
method to detect a possible shot at the time of the circuit breaker for pump power curve that has the 
APC box, so this should be set to alarm activated before the trigger point at which the circuit breaker is 

set. 
 
 

Summary of Contents for ABS APC 1/2B NG

Page 1: ...nal inscrita en el Registro Mercantil de Madrid Sulzer Pumps Wastewater Spain S A Avda de la Técnica 5 28522 Rivas Vaciamadrid Madrid www sulzer com ABS APC UP TO 1 Ó 2 PUMPS CONTROL PANEL BY SULZER PUMPS WASTEWATER SPAIN S A USER GUIDE ...

Page 2: ... 2 5 INSTALLATION RECOMMENDATIONS 2 6 CONTROL SYSTEM DESCRIPTION 3 OPERATION 3 1 AUTOMATIC SEQUENCES 3 2 SAFETY FACTORS 4 RECOMMENDED DOCUMENTS FOR READING 4 1 ELECTRICAL DRAWING 4 2 4 2FORM TO REGISTER PC242 SETTINGS 4 3 USER GUIDES fOR DEVICES RELATED TO APC CONTROL PANELS A LEVEL SENSORS MD124 MD126 MD127 USER AND INSTALLATION GUIDE B PC242 PUMPS CONTROLLER INSTALLATION GUIDE C PC242 PUMPS CONT...

Page 3: ... to the electrical net under any circumstances Before doing it make sure the control panel is completely disconnected We recommend you to contact to an authorized specialist company to install the control panel and connect the cables its personnel must known and follow the electrical rules technically and regarding safety and recommendations To avoid loosing the guaranty only Sulzer Pumps Wastewat...

Page 4: ...ersion and made by relays allowing working even if PC 242 were broken down in APC complete version Ready to receive a thermal sensor signal from each pump that could be bimetallic type PTC or PT100 PC 242 has an internal module to manage PTC and PT100 signals built in what allows to indicating the current temperature the sensor measures and set alarm set points Ready to receive a leakage sensor si...

Page 5: ... to PE terminal clamp 3 Same way you could see that thermal signal cables from pumps named F0 and F1 must be connected in terminal clamps Bn F0 and Bn F1 and leakage signal cables from pumps named DI and PE must be connected in terminal clamps Bn DI and Bn PE Some small pumps have power and signal wires in the same cable in that case you will not have a PE cable for power and other for signals not...

Page 6: ...to avoid pipe clogging as making a diagonal cut to the air pipe to have a bigger area of the side of the pipe submersed as it is shown at the left side picture When using an hydrostatic level sensor you must consider effects that could appear when installing the sensor hung from the pump pit top turbulences could make it hit itself with the sump walls or making a pendular movement that will could ...

Page 7: ...stop if the MCB the earth leakage switch or the thermal sensor were tripped or in case of motor drive failure It is thought mainly for tests during the pump station setting up and maintenance pump checks For safety reason it returns automatically to 0 you have to keep activating the selector for the period of time you want to retain the pump running avoiding to burn the motor by accident PUMP DISA...

Page 8: ...ES the PC 242 user and installation guides and the document named SETTINGS IN CONTROL PANEL MODEL APC2B COMPLETE PROGRAMMED FOR USING WITH LEVEL FLOATS specific for this project SEMI AUTOMATIC OPERATION SELECTOR IN AUTO APC control panel basic version has a semi automatic control system based on a PC 242 feature that runs the pumps if the high level float gets active what could happen in case of f...

Page 9: ...one common stop level float to the unit they will stop with a delay between stops See PC 242 user guide and the document named SETTINGS IN CONTROL PANEL MODEL APC2B COMPLETE PROGRAMMED FOR USING WITH LEVEL FLOATS specific for this project for more details or to learn how to change related settings Both starts and stops are done with a delay in between to avoid more than two or more pumps were star...

Page 10: ... apparent power power factor loads mains voltage etc PC 242 also allows you to trend graphs level curves consumption and flow pumping PC 242 enables advanced management of start and stop pumping before abrupt change in level function known as START EARLY IN CASE OF STORM It is able to start the pumps in advance to avoid overflows in the well if it detects sudden changes in level In rainwater pumps...

Page 11: ...to work in the highest area of the well pumping more caudal less consumption so you save energy by improving the performance and reducing working hours in addition to extending the life of the pump Also allows us to make emptying the pit to levels even lower than the normal stop before passing the stretch of arrival peak hour flow in order to avoid overflows PC 242 allows REMOTE CONTROL AND PROTEC...

Page 12: ...used for filling tanks or pumping catchment so that by default the APC box comes with this feature disabled if interested activate follow the user manual PC 242 and or implementation guide APC 2B frame HIGH LEVEL ALARM If you use an APC box with analogue level sensor and also shows the sump level in real time via the display in both graphical and numerical mode PC 242 allows you to generate alarms...

Page 13: ...oating contact general fault This alarm also for pumps and also signalled only helps the user PUMP NOT IN AUTO NOT AVAILABLE Each pump has a switch MAN AUT 0 in front of the box to set the operating mode in which we work If after handling is left in position 0 the pump is out of service To avoid this if after 60s the selector is not passed to AUTO PC 242 advised of this fact by an alarm text not i...

Page 14: ...of using general differential protection frame header used motor output protection to ensure the availability of pumps in pumping since in case of tripping earth leakage current in a pump or the feed cable or against nuisance tripping on start would act only protecting the pump leaving the rest available thus differential protection is especially important in pumping rainwater Fully finished in AP...

Page 15: ...ailure of motor control element a driver may drop etc CRITIC ALARM ALL PUMPS BLOCKED If a pump is blocked by PC242 due to an alarm or switch MAN AUT 0 to 0 and for some reason it blocks the other pump pumping out of service will be completely automatic To indicate this after some time of 30s PC242 generate an alarm by the alarm text B1 and B2 blocked We can consider this alarm criticism for any pu...

Page 16: ...APC that allows you to indicate if you want this system to act only with the pump B1 B2 with the pump or with both Once activated the alarm float pilot box excite alarm for warning buoy 2KA0 alarm and relay starting the pumps enabled it ie those selected with the selector 2S4 called SEMI COMPLETE APC and the operating mode selector to AUT Pump In Tables 23A over 2TIM1 timer is used to prevent acti...

Page 17: ...ee contacts for remote signalling 1 alarm per pump and 1 to indicate that PC 242 has an alarm s pending reset This can be seen easily in the extract of the wiring diagram in the following figure APC offers power output buzzer light alarm ABS 9000056 or similar As you can see in the figure above connect the warning signal or you can use the floating signal is desired along with the terminals AL and...

Page 18: ...G 4 1 ELECTRICAL DRAWING 4 2 FORM TO REGISTER PC242 SETTINGS 4 3 USER GUIDES FOR DEVICES RELATED TO APC CONTROL PANELS A LEVEL SENSORS MD124 MD126 MD127 USER AND INSTALLATION GUIDE B PC242 PUMP CONTROLLER INSTALLATION GUIDE C PC242 PUMP CONTROLLER USER GUIDE D PC242 PUMP CONTROLLER COMLI MODBUS REGISTER GUIDE ...

Page 19: ...l with references 84004263 84004264 84004265 84004266 84004307 84004308 84004511 84004512 84004513 84004514 84004515 84004516 84004517 84004518 84004519 84004520 84004521 84004522 84004523 84004524 To which this declaration relates are in conformity with the following standards or other normative documents IEC 158 1 2 IEC 364 1 7 IEC 255 1 IEC 408 IEC 337 1 IEC 204 1 2 IEC 158 IEC 292 CE 73 23 CE ...

Reviews: