FUNCTION AND USAGE

CA 462 is a combined standalone leakage detection and temperature blocking 
relay for DIN rail mount. 

1.1 

Function leakage

In case of water leakage, the resistance between the sensor electrode and hous-
ing will decrease. If the resistance becomes less than 100 kohm (±10 %) between 
terminals 11 and 12, the relay contact on terminal 1 and 2 closes. The signal has 
to be stable for at least 10 seconds before the relay is been activated.

1.2 

Function Temperature blocking

If the temperature in the pump is rising and the terminal protector sets off, the 
CA 462 is blocking the pump without any delay. 

Automatic reset

−  

if terminal 14 and 15 are open;

 pump starts automatically when the tempera-

ture is back to normal.

Manual reset

− 

 

if terminal 14 and 15 are bridged;

 manual reset has to be done by terminal 13 

and 14 after the temperature is back to normal.

Table 1: 

Connection chart

Terminal

Description

1

Leakage Alarm Relay (NO)

2

Leakage Alarm Relay

3

High Temperature Alarm Relay (NO)

4

High Temperature Alarm Relay

5

Pump Relay (NO) (Closed under normal operation)

6

Pump Relay

7

Power Supply (0 V 

or

 N)

8

Power Supply (+24 VDC 

or

 L1)

9

Input from pump temperature sensor (PTC / Klixon)

10

Input from pump temperature sensor (PTC / Klixon)

11

Input from pump leakage probes

12

Connect to Ground or Pump chassis

13

Reset switch for high temperature alarm

14

Reset switch for high temperature alarm

15

Manual reset required if bridged  to terminal 14*

* If bridged to terminal 14; manually reset is required after high temperature alarm 

after

 condi-

tion is back to normal. If 

not

 bridge; pump start automatically when condition is back to normal.

Table 2: 

Product reference

Article

Description

16907006

CA 462 110-230 VAC Supply voltage 

16907007

CA 462 18-36 VDC Supply voltage

One item of Xylem MiniCas adapter is included in both 16907006 and 16907007.

Temperature and leakage relay type ABS CA 462, Installation guide

  

EN

 81907004H

Summary of Contents for CA 462

Page 1: ...www sulzer com CA 462 Temperature and Leakage Relay Type ABS CA 462 EN Installation Guide 81907004I 11 2017 CA 462 ...

Page 2: ... a commitment by Sulzer Sulzer assumes no responsibility or liability for any errors or inaccuracies that may appear in this book Except as permitted by such license no part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical recording or otherwise without the prior written permission of Sulzer Sulzer reserves the righ...

Page 3: ...normal Table 1 Connection chart Terminal Description 1 Leakage Alarm Relay NO 2 Leakage Alarm Relay 3 High Temperature Alarm Relay NO 4 High Temperature Alarm Relay 5 Pump Relay NO Closed under normal operation 6 Pump Relay 7 Power Supply 0 V or N 8 Power Supply 24 VDC or L1 9 Input from pump temperature sensor PTC Klixon 10 Input from pump temperature sensor PTC Klixon 11 Input from pump leakage ...

Page 4: ...Pump 5 6 Alarm 4 3 Leak 2 1 closed open closed open open Normal operation Temperature Yes 3 3 kohm open open closed open Pump stops Leakage Yes closed 100 kohm closed open closed Pump runs Temp Leak Yes Yes 3 3 kohm 100 kohm open closed closed Pump stops EN Temperature and leakage relay type ABS CA 462 Installation guide 81907004H ...

Page 5: ...AGRAM CA 462 Figure 1 Electrical connection diagram Figure 2 Dimensions EN Temperature and leakage relay type ABS CA 462 Installation guide 81907004H 130 mm 5 13 108 mm 4 25 70 mm 2 76 60 mm 2 36 58 mm 2 28 108 mm 4 25 ...

Page 6: ...relay The output to MiniCas is polarity independent CA 462 Figure 3 Connection diagram for MiniCAS adapter Table 5 Logic diagram of output resistance related to the inputs Temperature Input Seal Leak Input Output Resistance OK OK Nominal 1500 Ω OK Seal failure Condition LOW 400 Ω Over temperature Condition open or disconnected OK or Seal Failure Condition HIGH 4000 Ω EN Temperature and leakage rel...

Page 7: ...e V0 E45329 Humidity 0 95 RH non condensing Dimensions H x W x D 108 x 70 x 58 mm 4 25 x 2 76 x 2 28 inch Power supply 16907006 110 230 VAC 16907007 18 36 VDC SELV or Class 2 Fuse Max 10 A Terminal wire size Use copper Cu wire only 0 2 2 5 mm2 flexible core stripped length 8 mm Terminal tightening torque 0 56 0 79 Nm 5 7 lbs in Power consumption 5 W Max load alarm relays 250 VAC 3 Ampere resistive...

Page 8: ...ld be the microfiber type of cloth and gently wipe the CA 462 unit on front in order not to scratch the overlay If the dry cloth did not completely remove the dirt do not press harder in an attempt to scrub it off If necessary moisten the cloth by adding a small amount of water with thin solution of mild detergent and try again Never use detergent with polish or solvent which can have an impact of...

Page 9: ... sole responsibility that the products SV Försäkrar under eget ansvar att produkterna DE Erklärt eigenverantwortlich dass die Produkte NO Erklærer på eget ansvar at følgende produkter FR Déclarons sous notre seule responsabilité que les produits DA Erklærer på eget ansvar at følgende produkter NL Verklaren geheel onder eigen verantwoordelijkheid dat de produkten FI Vakuutamme yksinomaan omalla vas...

Page 10: ...Sulzer Pump Solutions Ireland Ltd Clonard Road Wexford Ireland Tel 353 53 91 63 200 Fax 353 53 91 42 335 www sulzer com Copyright Sulzer Ltd 2017 ...

Reviews: