72
| Optidrive P2 User Guide |
Version 3.07
www.invertekdrives.com
10. Technical Data
10.1. Environmental
Ambient
Temperature
Storage and Transportation
All Units
-40 … 60°C / -40 … 140°F
Operating
IP20 Units -10 … 50°C / 14 … 122°F
IP55 Units - 10 … 40°C / 14 … 104°F
UL Approved
40 … 50°C / 104 … 122°F
With derating (refer to section
Ambient Temperature on page 75
)
IP66 Units - 10 … 40°C / 14 … 104°F
UL Approved
40 … 50°C / 104 … 122°F
With derating (refer to section
Ambient Temperature on page 75
)
Altitude
Operating
All Units
=<1000m
With UL approval
=<4000m
With derating (refer to section
)
Relative Humidity
Operating
All Units
< 95%
Non-condensing, frost and moisture free
10.2. Input/Output Power and Current Ratings
The following tables provide the output current rating information for the various Optidrive P2 models. Invertek Drives always
recommend that selection of the correct Optidrive is based upon the motor full load current at the incoming supply voltage.
Please note that the maximum cable length stated in the following tables indicate the maximum permissible cable length for the drive
hardware and does not take into consideration EMC compliance.
10.2.1. 200 – 240 Volt (+/- 10%),1 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated
Output
Current
Maximum
Motor Cable
Length
Recommended
Brake
Resistance
kW
HP
A
Non UL
UL
mm
AWG/kcmil
A
m
ft
Ω
2
0.75
1
8.6
16
15
8
8
4.3
100
330
100
2
1.5
2
12.9
16
17.5
8
8
7
100
330
50
2
2.2
3
19.2
25
25
8
8
10.5
100
330
35
10.2.2. 200 – 240 Volt (+/- 10%), 3 Phase Input, 3 Phase Output
Frame
Size
Power
Rating
Input
Current
Fuse or MCB
(Type B)
Maximum Cable
Size
Rated
Output
Current
Maximum
Motor Cable
Length
Recommended
Brake
Resistance
kW
HP
A
Non UL
UL
mm
AWG/kcmil
A
m
ft
Ω
2
0.75
1
5.7
10
10
8
8
4.3
100
330
100
2
1.5
2
10.5
16
15
8
8
7
100
330
50
2
2.2
3
13.2
16
17.5
8
8
10.5
100
330
35
3
4
5
20.9
32
30
8
8
18
100
330
20
3
5.5
7.5
26.4
32
35
8
8
24
100
330
20
4
7.5
10
33.3
40
40
16
5
30
100
330
22
4
11
15
50.1
63
70
16
5
46
100
330
22
5
15
20
63.9
80
80
35
2
61
100
330
12
10
Technical Data