4.2. Protective Earth (PE) Connection
4.2.1. Grounding Guidelines
Adequate safety earthing must be provided in accordance with local wiring rules and codes of practice. The ground terminal of
each Optidrive should be connected back to the common safety earth bar to maintain touch potentials within safe limits. The ground
terminal of each Optidrive should be individually connected DIRECTLY to the site ground bus bar (through the EMC filter if installed).
Optidrive ground connections should not loop from one drive to another, or to, or from any other equipment. Ground impedance must
conform to local industrial safety regulations and/or electrical codes.
To meet UL regulations, UL approved ring crimp terminals should be used for all ground wiring connections.
The integrity of all ground connections should be checked periodically.
4.2.2. Protective Earth Conductor
The Cross sectional area of the PE Conductor must be at least equal to that of the incoming supply conductors.
4.2.3. Motor Ground
The driven motor must be locally connected to a suitable ground location to maintain touch potentials within safe limits. In addition, the
motor ground must be connected to one of the ground terminals on the drive.
4.2.4. Ground Fault Monitoring
As with all inverters, a leakage current to earth can exist. The Optidrive is designed to produce the minimum possible leakage current
whilst complying with worldwide standards. The level of current is affected by motor cable length and type, the effective switching
frequency, the earth connections used and the type of RFI filter installed. If an ELCB (Earth Leakage Circuit Breaker) is to be used, the
following conditions apply:
A Type B Device must be used.
Individual device should be used for each Optidrive.
The device must be suitable for protecting equipment with a DC component in the leakage current.
The device should be not sensitive to high frequency leakage current.
4.2.5. Shield Termination (Cable Screen)
The safety ground terminal provides a grounding point for the motor cable shield. The motor cable shield connected to this terminal
(drive end) should also be connected to the motor frame (motor end). Use a shield terminating or EMI clamp to connect the shield to
the safety ground terminal, refer to section
4.13. EMC Compliant Installation
4.3. Incoming Power Connection
NOTE
For IP20 Frame Size 8 it is important that the input supply phase orientation is correct, i.e. L1>L1, L2>L2, L3>L3, failure to do so
will result in a “
Ph-Seq
" trip.
Ensure there is at least 30 seconds between each power-on.
4.3.1. Suitability
All Optidrive P2 models are designed for use on a single phase or balanced three phase supply depending on the model.
For all models and ratings when working with an IT Supply network, or any power supply type where the phase to earth voltage may
exceed the phase to phase voltage (such as ungrounded supplies), the internal EMC filter and surge protection must be disconnected before
connecting the supply. Refer to section
10.6. Internal EMC Filter and Varistors – Disconnection Procedure on page 76
for further information.
For three phase supply models, a maximum of 3% imbalance is allowed between phases.
4.3.2. Cable Selection
For 1 phase ac supply, power should be connected to L1/L, L2/N.
For a DC Supply, the main power cables should be connected to L1/L, L2/N.
For 3 phase ac supplies, the mains power cables should be connected to L1, L2, and L3. Phase sequence is not important. Neutral
connection is not required.
For compliance with CE and C Tick EMC requirements, refer to section
4.13. EMC Compliant Installation
A fixed installation is required according to IEC61800-5-1 with a suitable disconnecting device installed between the Optidrive
and the main Power Source. The disconnecting device must conform to the local safety code / regulations (e.g. within Europe,
EN60204-1, Safety of machinery).
The cables should be dimensioned according to any local codes or regulations. Maximum dimensions for each drive model are
10.2. Input/Output Power and Current Ratings
4.3.3. Fuse / Circuit Breaker Selection
Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply line, according to
the data in section
10.2. Input/Output Power and Current Ratings
The fuses must comply with any local codes or regulations in place. In general, type gG (IEC 60269) or UL type J fuses are
suitable (exception: Eaton Bussmann FWP series must be used for size 6A & 6B IP20 models); however in some cases type aR
fuses may be required. The operating time of the fuses must be below 0.5 seconds.
Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in
place of fuses, providing that the clearing capacity is sufficient for the installation.
The maximum permissible short circuit current at the Optidrive Power terminals as defined in IEC60439-1 is 100kA.
The Optidrive provides thermal and short circuit protection for the connected motor and motor cable.