background image

6

SECTION 1V

Panel Display, Switches and Circuit Breaker

Located in the upper front right-hand side of the furnace is the control panel containing the indicating light (LED).

LED Indications

The green LED on the front of the furnace directly above the thermostat terminal strip displays the current status of the furnace.

A slow blinking LED, once every 3 seconds indicates that the furnace is powered and in standby mode.

A moderately fast blinking LED, once per second indicates that either a heating or a cooling cycle is in progress.

A rapidly blinking LED, 5 times per second indicates that the furnace is completing a heating cycle and that the heating elements 

are cooling down.

The upper rocker switch selects our exclusive Comfort Max feature. 

Options Dip Switches 1,2,3,4 ( Refer to wiring diagram)

Should the LED located at the top of the thermostat terminal strip display RED, this is an indication that the switch positions on the 

options dipswitch on the controller have either been changed or that the switch itself has failed.

Confirm correct setting.

Switch 1  - ON, Switch 2  - OFF, Switch 3  - OFF, Switch 4  - ON

If the switch positions are correct and fully seated and problem persists, replace controller.

Options Dip Switches A,B,C

These switchs are used to select the correct BTUH output of the furnace.

See chart below.

Quiet Comfort Feature

This switch is used to select the Quiet Comfort Feature.

When switch D turned ON and the Continuous Fan switch on the furnace is switched ON, one heating element is operated at 50% 

output.

This will provide a slight warming of the recirculated air eliminating the feeling of drafty air being circulated.

When the Quiet Comfort feature has been activated at Switch D, The LED on the front of the furnace will blink Orange.

The lower rocker switch enables continuous low speed fan operation.

The furnace mounted circuit breaker on the right provides fan motor over amp protection to 16 amps.

This circuit protection only applies to the fan motor. 

The Heating element circuit breaks provide overload circuit protection in the event one or more of the heating elements should fail.

Should this happen, one or more of the circuit breakers will trip to the off position.

Do not attempt to reset the breaker or access the control panel.

Call a licensed servicing contractor immediately.

Cooling Defrost

When used with a Heat Pump and ice is detected on external unit, this will add a little heat to refrigerant lines to de-ice.

LED:   Amber Medium Flash 2 times per second

BTU SETTING TABLE (OPTION SWITCHES)

OPTION

5KW

10KW

15KW

18KW

20KW

23KW

27KW

A

OFF

ON

OFF

OFF

OFF

ON

OFF

B

OFF

OFF

ON

OFF

OFF

OFF

ON

C

OFF

OFF

OFF

ON

ON

ON

ON

Summary of Contents for SE10I (E)

Page 1: ... Commissioning checklist 9 Model specifications 10 DRAWINGS and ILLUSTRATIONS Blower shipping support bracket 2 Installation orientation 4 Two stage heating output 9 Furnace specifications 10 Wiring Diagrams 11 For Service Please Call INSTALLATION INFORMATION _________________ _________________ Qualified Contractor Telephone Number _________________ _________________ Unit Model Number Unit Serial ...

Page 2: ...ing or heat pumps INSTALLATION OVERVIEW Install this appliance in accordance with these instruction and all national and local building safety codes and requirements Only connect this furnace to a duct system with a maximum static pressure of 0 6 Static pressures in excess will result in reduced air flow and potential elevated discharge air temperatures during heating cycles and reduced discharge ...

Page 3: ...is available for counter flow installations on combustibles Adequate access must be provided at the front of this furnace for service For horizontal installations it is recommended to use steel angle support brackets with threaded rods supporting the unit from the bottom Refer to Fig 1 Due to the hazardous nature of electrical and mechanical requirements only trained and qualified personnel should...

Page 4: ...able balanced delivered air All duct work should be designed fabricated and installed in accordance with all national and or local codes Air Filters Included with this furnace is a 20 x 20 x 1 disposable air filter and supporting filter rack This filter rack shall be secured to the furnace casing on either side or the bottom Do not install this filter rack on the front or back of the furnace Doing...

Page 5: ...direct drive motors or ECM motors Furnaces up to and including 23kW outputs are provided with 1 3 hp 3 speed motors 27kW furnaces are provided with 3 4hp 4 speed motors Only 3 speeds are connected to the controller The fourth speed motor lead low speed is not connected Low Voltage Contained within the control enclosure is the low voltage transformer This is 240vac primary with 24vac secondary 40 V...

Page 6: ... B C These switchs are used to select the correct BTUH output of the furnace See chart below Quiet Comfort Feature This switch is used to select the Quiet Comfort Feature When switch D turned ON and the Continuous Fan switch on the furnace is switched ON one heating element is operated at 50 output This will provide a slight warming of the recirculated air eliminating the feeling of drafty air bei...

Page 7: ... and homeowner comfort The ComfortMAX Option for Heating is selected by a switch on the front panel of the appliance When the switch is activated during a call for heat the control will only activate the number of elements that are estimated to be needed to satisfy the call for heat within a 13 to 18 minutes If the call for heat is satisfied in less than 13 minutes the number of heating elements a...

Page 8: ...E ADJUSTMENT TAP SWITCH POSITIONS AFFECTS BOTH THE HEATING AND COOLING FAN SPEEDS OFF OFF DOES NOT CHANGE SELECTED AIR FLOWS ON OFF INCREASES AIR FLOWS APPROXIMATELY 10 OFF ON REDUCES AIR FLOWS APPROXIMATELY 15 HEATING TAP SWITCH POSITION NOTE TURN POWER OFF BEFORE MAKING A SELECTION HEATING TAP BOARD SWITCHES 1 AND 2 AIR FLOW CFM EXTERNAL STATIC PRESSURE WC 0 2 0 5 0 7 OFF OFF 1250 1400 1400 ON O...

Page 9: ... side of furnace 2 Thermostat is not connected to controller 3 A C condenser is connected 4 Ground is securely connected at furnace ground lug and main panel 5 Incoming power lines are connected and secure at main terminal block 6 Continuous fan switch is set to off 7 Comfort max switch on furnace side panel is set to OFF Sequence 1 a Place a jumper across thermostat terminals R and W on terminal ...

Page 10: ...S 43 63 83 92 95 114 MINIMUM CIRCUIT AMPS 60 85 100 110 125 150 BREAKER SIZE AMPS 60 90 100 125 125 150 WIRE SIZE AWG 6 4 3 3 2 1 BLOWER DATA PSC Fan motor design only HEATING BLOWER SPEED 0 50 E S P MED LOW MED LOW MED HIGH MED HIGH MED HIGH MED HIGH BLOWER SPEED 0 20 E S P MED LOW MED LOW MED HIGH MED HIGH MED HIGH MED HIGH MOTOR H P SPEEDS PSC 230V 1 3 HP 3 SPEED 3 4 HP 4 SPEED ECM 230V 1 3 HP ...

Page 11: ...CT SWITCH 220 VAC L2 220 VAC L1 HIGH MED ACC CONT FAN LEGEND BR1 CIRCUIT BREAKER BR2 CIRCUIT BREAKER BR3 CIRCUIT BREAKER HL HIGH LIMIT EL ELECTRIC ELEMENT R ELEMENT RELAY OPTIONS DIP SWITCH COMFORT MAX SWITCH ON Remove W W2 jumper when a 2 stage heating thermostat is used or when activating Comfort Max mode Remove Y Y2 jumper when a connecting to 2 stage cooling ...

Page 12: ... SWITCH 4 2 BRKR16A 16A BREAKER 5 2 RELAYSEI HEATING ELEMENT RELAYS 6 2 BRD9400I MAIN CONTROL 7 2 CVR9400I CONTROL COVER 8 2 TRANSEB TRANSFORMER 9 2 MTR1972 2 MTREON MOTOR 10 2 CAP MOTOR CAPACITOR 11 2 MTRBRKT557 BLOWER MOTOR BRACKET NOT SHOWN 12 2 BLWRG10DD BLOWER 13 2 BRKR50 50A CIRCUIT BREAKER 14 2 BRKR25 25A CIRCUIT BREAKER 15 2 LIMCONT120100 HIGH LIMIT 16 2 TBMAIN MAIN TERMINAL BLOCK Fig 6 ...

Page 13: ..._REV9 Specifications and illustrations subject to change without notice and without incurring obligations Trent Metals Limited Summeraire Manufacturing Peterborough ON Canada K9J 7B1 Phone 705 745 4736 www summeraire com ...

Reviews: