Installation Procedure
37
Install the Rear AC Sequencer, Hub, and
Remote Power Control Module Shelf
Install the AC sequencer, hub, and RPCM in the rear 4U panel (See
Note –
If AC sequencers and hubs are mounted in external racks or cabinets then
blank panels are installed in their place on the 4U panel as described in “Alternate
4U Panel Installation”.
1. Connect the one end of the AC line cord to the connector on the rear of the hub.
Make sure the RJ-45 connectors are oriented toward the upper half as shown in
.
2. Install the hub all the way to the right in the 4U panel.
Fasten the hub with 10-32 screws and tighten them fully.
3. Retrieve the loose end of the ground cable and let it hang out of the 4U panel.
4. Connect the free end of the AC line cord into J6 on the rear panel of the AC
sequencer.
5. Install the AC sequencer next to the hub.
Install the bottom of the AC sequencer first then swing the top into position. Fasten
the AC sequencer with four 10-32 screws and tighten them fully.
6. Attach the free end of the ground cable to the front of the AC sequencer with a
M5x12 screw.
7. Install the RPCM shelf in the 4U panel.
Fasten the RPCM shelf with 10-32 screws and tighten them fully.
8. Install the RPCMs in the RPCM shelf.