1-8
Sun Fire B1600 System Chassis Hardware Installation Guide • August 2003
1.5
Site Preparation
This section contains information about the following system and site requirements
for the Sun Fire B1600 blade system chassis:
■
Section 1.5.1, “System Cooling Requirements” on page 1-8
■
Section 1.5.2, “Operating Power Limits and Ranges” on page 1-12
■
Section 1.5.3, “Estimating Power Consumption” on page 1-12
1.5.1
System Cooling Requirements
This section provides the general environmental parameters and airflow
requirements for the Sun Fire B1600 blade system chassis.
Note –
The Sun Fire B1600 blade system chassis uses front-to-back forced air
cooling.
1.5.1.1
General Environmental Parameters
You can operate and store the system safely in the conditions detailed in
and
TABLE 1-2
Operating and Storage Specifications
Specification
Operating
Storage
Ambient temperature
5˚C to 35˚C
maximum ambient
temperature is derated by 1˚C
per 500m altitude above 500m
-40˚C to 65˚C
Relative humidity
10% to 90% RH non-
condensing, 27˚C max wet
bulb
up to 93% RH non-
condensing, 38˚C max wet
bulb
Altitude
-400m up to 3000m
-400m up to 12000m
Summary of Contents for Sun Fire B1600 Administration
Page 6: ...vi Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 10: ...x Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 14: ...xiv Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 30: ...2 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 82: ...5 14 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 94: ...6 12 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 98: ...Index 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...