Export 1-Pump Cayman / Lagunas Models (50Hz)
230V/20A*
230V/30A**
Voltage:
230 VAC
230 VAC
# of Wires:
3
3
Frequency:
50Hz
50Hz
Current Draw:
15A
21A
Circuit Breaker:
20A
30A
*
In the 20A configuration, the heater
will not operate
at the same time as
the main jets pump.
This is the factory setting.
**
In the 30A configuration, the heater
will operate
at the same time as
the main jets pump.
Export 2-Pump Palermo / Bahia Models (50Hz)
230V/20A*
230V/30A**
230V/40A***
Voltage:
230 VAC
230 VAC
230 VAC
# of Wires:
3
3
3
Frequency:
50Hz
50Hz
50Hz
Current Draw:
15A
23A
29A
Circuit Breaker:
20A
30A
40A
*
In 20A configuration, the heater
will not operate
while either jets
pump
is running in high speed.
This is the factory setting.
Note: pump 2
runs only in high speed.
**
In 30A configuration, the heater
will not operate
while both jets pumps
are running in high speed.
Note: pump 2 runs only in high speed.
***
In 40A configuration, the heater
will operate
while either jets pump
is running in high speed. Note: pump 2 runs only in high speed.
US/Canada 2-Pump Palermo / Bahia Models (60Hz)
240V/50A*
240V/30A**
240V/60A***
Voltage:
240 VAC
240 VAC
240 VAC
# of Wires:
3
3
3
Frequency:
60Hz
60Hz
60Hz
Current Draw:
36A
24A
43A
Circuit Breaker:
50A, 2-Pole
30A, 2-Pole
60A, 2-Pole
*
In 50A configuration, the heater
will not operate
while both jets pumps
are running in high speed.
Note: pump 2 runs only in high speed.
This is
the factory setting.
**
In 30A configuration, the heater
will not operate
while either jets pump
is running in high speed.
Note: pump 2 runs only in high speed.
***
in 60A configuration, the heater
will operate
while both jets pumps are
running in high speed.
Note: pump 2 runs only in high speed.