background image

© 2015 SunEdison 

8

F-SERIES and R-SERIES 

72-Cell Installation Guide

4.0  Electrical Installation 

4.1  Planning and Design 

All modules are manufactured with a sealed junction 
box, pre-attached cables and locking connectors. These 
components should not be modified or tampered with 
in any way.

Note: 

Installers shall ensure that the polarized locking 

connectors are from the same supplier. Do not mix 
polarized interlocking connectors from different 
manufacturers—including connections at the inverter, 
combiner boxes and modules. Doing so will void the 
warranty. Refer to the corresponding data sheet for 
connector types.

 

• Ensure connectors are clean and dry before 

establishing connection. 

 

• Ensure that all wire, fusing and disconnects are 

appropriately sized for the system design according 
to national, regional, and local codes. 

 

• Electrical characteristics are within plus or minus 5% of 

rated values for Isc, Voc, Impp and Vmp. Pmax ranges 
between 0% to +3% (R-Series) and 0 W to +5 W 
(F-Series) of rated Pmax at standard test conditions 
(STC). However, modules will operate under conditions 
that may be significantly different than STC. SunEdison 
suggests multiplying specified ratings by a minimum of 
1.25 or more when designing the system and balance 
of system components. Refer to local codes before 
planning and designing the system.

 

• Determine the maximum number of modules that may 

be connected in series using the following formula 

Ns = Vmaxs/Vocm

Where:

Ns

 equals the maximum modules in series.

Vmaxs

 equals the maximum system voltage.

Please refer to module data sheet for actual Vmax 
rating, as some models are rated for 1000 V UL and 
1000 V IEC.

Vocm

 equals the module open circuit voltage at 

coldest conditions for the site (refer to local codes).

4.2  Module Wiring

 

• The module includes wires and polarized locking 

connectors from the junction box on the back of the 
module. Field replacement of connectors or cables 
must be avoided and will void the product warranty. 
Polarized locking connectors of the same type, make 
and manufacturer are required for all series string 
wiring. The maximum operating temperature of the 
wires and connectors should not exceed 85 C.

 

• When installing modules in landscape orientation, use 

the 1.3 meter lead lengths to ensure enough cable 
length to make adjacent module-to-module string 
connections (assumes a maximum spacing of 50 mm 
between adjacent modules).

 

• Always wire modules so that proper polarity is 

maintained. Avoid placing excessive tension on 
the cables.

 

• There is no limit to the maximum number of series 

strings that can be combined in parallel. However, 
each string must include overcurrent protection with a 
maximum rating of 15 A. SunEdison recommends the 
use of DC rated fuses or overcurrent protection devices 
with the appropriate maximum voltage rating. 

 

• Do not connect modules directly to a parallel bus. 

 

• The cross-sectional areas of cable and the connector 

type must be selected to align with the overall system 
design, and should include the maximum short 
circuit current of the system, maximum operating 
temperatures and cable run lengths. 

 

• For field connections, use at a minimum #12 AWG/4 

mm

2

 wires; insulated for a minimum of 85 C. Use 

copper wire only. 

WARNING:

 

Installers shall adhere to all applicable local, regional, and national codes and regulations when designing 

and constructing the photovoltaic system

Note: 

In colder climates, it may be necessary to further reduce the maximum number of modules in a series by using 

Vocm at the minimum expected operating temperature.

Summary of Contents for Silvantis F310BzC

Page 1: ...SILVANTIS PHOTOVOLTAIC MODULES F SERIES and R SERIES INSTALLATION GUIDE 72 Cell High Wattage Modules ...

Page 2: ...d by Installation Guide Silvantis Monocrystalline Modules Silvantis F Series F310BzC F315BzC F320BzC F325BzC F330BzC F335BzC Silvantis F Series U S Tariff Free F310BzD F315BzD F320BzD F325BzD F330BzD F335BzD Silvantis R Series R330BzC R335BzC R340BzC R345BzC R350BzC R355BzC z indicates manufacturing location M Malaysia X Mexico K Korea P China T Taiwan For product parameters and specifications see...

Page 3: ... modules with sharp instruments Do not leave a module unsupported or unsecured Do not modify module in any way which includes the frame glass eva etc Upon unpacking only carry a module by its frame with two or more people Do not carry a module by the wires or junction box All modules are manufactured with a sealed junction box pre attached cables and locking connectors These components should not ...

Page 4: ...sed in 2014 all Silvantis solar modules also have a module fire resistance rating of Class A for spread of flame and fire performance of either Type 1 or Type 2 classification as specified on the module label Per UL the fire rating of this module is valid only when mounted in the manner specified in the mechanical mounting instructions The system fire rating is determined by the module rack and ro...

Page 5: ... fixing or clamping force torque the fasteners to the manufacturers torque specifications For all cases the area of the supporting structure in contact with rear side of the module must comply with the dimensions specified in Appendix 7 1 All other structural dimensions such as clamp and rail thickness should be sized appropriately for the intended site load 3 3 Module Installation Using Center Mo...

Page 6: ...the module should be fixed via bolts at the mounting holes between each long side frame or Clamps can be mounted at the Fixed Clamp Mount location as shown in the color code key See 7 3 for minimum clamp dimensions CASE 2 Structural rails running parallel to the length of the module should be fixed via bolts at the mounting holes on each long side frame or Clamps can be mounted anywhere within the...

Page 7: ...le Axis Tracker is authorized for use as well Please refer to the AP90 installation guide for specific instructions Installation guides can be found on the SunEdison website Maximum Rear Load 2400 Pa 50 psf Maximum Front Load 2400 Pa 50 psf CASE 4 Structural rails running parallel to the length of the module should be attached within the Mounting Range on each long side frame as shown in the color...

Page 8: ...le open circuit voltage at coldest conditions for the site refer to local codes 4 2 Module Wiring The module includes wires and polarized locking connectors from the junction box on the back of the module Field replacement of connectors or cables must be avoided and will void the product warranty Polarized locking connectors of the same type make and manufacturer are required for all series string...

Page 9: ...ding method A copper grounding wire with a minimum gauge of 12 AWG is recommended to carry the electrical ground load Consult applicable codes to ensure the appropriate conductor diameter is used for the system The grounding method must not allow direct contact of dissimilar metals with the frame of the module as this would result in galvanic corrosion UL 1703 recommends metal combinations not to ...

Page 10: ... M4 Stainless Steel Lock Toothed Washer M4 Stainless Steel Slotted Washer M4 English set Stainless Steel Bolt 8 32 Stainless Steel Nut 8 32 Stainless Steel Flat Washer 8 32 Stainless Steel Spring Washer 8 32 Stainless Steel Lock Toothed Washer 8 32 Stainless Steel Slotted Washer 8 32 Step 1 Place the grounding lug over the grounding hole on the exterior of the module frame Step 2 Place a star wash...

Page 11: ...te both module and structure Should you choose a rack integrated method that is not approved by UL please contact SunEdison before proceeding to determine compatibility 4 3 Option C Bolt Wire Assembly Step 1 Attach grounding lug at one of the designated aforementioned grounding hole locations Using only stainless steel hardware insert a stainless steel bolt first through the stainless steel cup wa...

Page 12: ...he product warranty Do not wash modules with water that is more than 20 C cooler than the surface of the module Doing so can cause the glass to crack WARNING Use caution when cleaning the back surface of the module to avoid scratching the substrate materials 5 1 String Grounding Silvantis F series modules come in two types PID free and PID resistant PID free panels have a PID free designation on t...

Page 13: ... warranty SunEdison will not be held liable for special indirect consequential contingent or incidental damages related to or arising from the installation or use of the product by purchaser under any circumstances SunEdison assumes no responsibility for any product application or use that is beyond SunEdison s direct control SunEdison does not accept responsibility and expressly disclaims liabili...

Page 14: ...ERS Module Weight 22 kg Frame Material Anodized aluminum alloy Tempered ARC Glass Thickness 3 2 mm Connector Types Amphenol H4 39 Dimension mm inch Module Dimensions A 990 39 0 B 1 976 77 8 C 50 2 0 D 30 1 2 E 22 0 9 Dimension mm inch Mounting Hole Spacing F 950 37 4 G 1 188 46 8 P 400 15 7 Cable Length H 1 300 51 2 ...

Page 15: ...RAMETERS 7 3 Module Clamp Drawings Bolt Stack Details Center Mount Option 7 2 Center Clamp Module Installation Illustrations Dimension mm inch Module Clamp Dimensions A 6 35 0 25 B 38 1 5 Minimum Clamp Dimensions C 50 1 97 D 15 0 59 ...

Page 16: ...pper Drive Belmont CA 94002 Phone 866 786 3347 or 650 453 5600 Fax 443 909 7150 2015 SunEdison Products Singapore Pte Ltd A SunEdison Company All rights reserved SunEdison and the SunEdison logo are registered trademarks or trademarks of SunEdison Products Singapore Pte Ltd and or its affiliates in the United States and certain other countries All other trademarks mentioned in this document are th...

Reviews: