58
When the Logger1000 is connected to a device via the serial port, the baud
rate, parity bit, and stop bit of the serial port should be the same as those set
for the connected device, so as to ensure normal communication between the
Logger1000 and the connected device. The baud rate is 9,600bps, stop bit is
1, and there is no parity bit by default.
9.10.10.2 Ethernet
Perform Ethernet settings on this interface.
Step 1
Click "System" -> "Port Parameter" -> "Ethernet" to enter the corresponding interface.
Step 2
If auto IP allocation is “
”, it is recommended to obtain the current IP address of
the ETH port by connecting the WiFi module and logging into 11.11.11.1.
Step 3
If the parameter "Automatically obtain IP settings (DHCP)" is set to “
” fill in the
information such as the IP address, subnet mask, and default gateway, and click the
button
to save the operation.
-- -- E
En
nd
d
The default IP address of the ETH port is 12.12.12.12.
If both auto IP allocation and WiFi STA client are enabled, ensure that the
Ethernet and the WiFi STA are at different network segment. Otherwise, it is
probably that neither of the two networks is available.
9.10.10.3 Mobile network
Perform Mobile network setting on this interface.
Step 1
Click "System" -> "Port Parameter" -> "Mobile Network" to enter the corresponding
interface.
Step 2
After modifying the APN, username and password, click
to save the information.
-- -- E
En
nd
d
9.10.10.4 WiFi
Perform WiFi setting on this interface.
W
WiiF
Fii S
ST
TA
A c
clliie
en
ntt
WiFi STA refers to a case in which the Logger1000 connect to another hotspot or router
via the WiFi function.
Click "System" -> "Port Parameter" -> "WiFi" to enter the corresponding interface. Users
will enter the client mode by default, and the WiFi switch is closed.
User Manual