31
•
Default IP address of the ETH2 port is 13.13.13.13.
•
If the ETH2 port has enabled the Dynamic Host Configuration Protocol (-
DHCP) function, the IP address of the port can be read out after the it is
connected to a router or other devices.
7.8
Connecting to the AC Power Supply
The Logger3000 can be connected to a power source with voltage ranging from 100 to
277Vac.
step 1
Lead the external power supply cable to the wiring area of the Logger3000.
step 2
Strip the power supply cable by an appropriate length and crimp it to an euro style
terminal.
step 3
Insert the euro style terminal to the external jack "AC100~277V" of the Logger3000.
-- -- E
En
nd
d
The Logger3000 can be connected to both AC power supply and DC power
supply. UPS can be used as a DC backup power source.
7.9
Connecting to the DC Power Supply
The Logger3000 can be connected to 24Vdc external power supply. UPS can be used
as a power source.
step 1
Lead the external power supply cable to the wiring area of the Logger3000.