71
table 10-6
Parameter description
P
Pa
arra
am
me
ette
err
D
De
essc
crriip
pttiio
on
n
Scheduling mode
Logger4000 is connected to the power plant dispatch server
designated by the Japan Electric Power Company to achieve
Kyushu electric power dispatching or Hokkaido electric
power dispatching.
Obtaining Schedule
Support remote download and local import
When it is set to "Remote download", fill in plant code and
server address, and import certificate, to download schedule
from the set server address.
When it is set to "Local import", just import the schedule file.
Parameter type
Select "Plant parameter" or "Device parameter".
When selecting "Plant parameter", set plant capacity and PV
module capacity further.
When selecting "Device parameter", click "Detailed device
parameter" to view and set device information.
Time calibration
Calibrate the time as needed. Calibration range: -10~10.
When the system time of Logger4000 < the time adjusted
after "Time calibration", or the time of Logger1000 < the NTP
synchronization time,
The time validity will be displayed as "Invalid", at which time
Logger1000 will send a stop instruction to the inverter.
"Time validity: Invalid" will not disappear until the "Time
calibration" or NTP synchronization operation is performed.
-- -- E
En
nd
d
10.2.1.7 Scheduling Prohibited
Set the active control mode to "Scheduling prohibited" if the Logger4000 is prohibited to
perform active dispatching on the inverter.
step 1
Click "Power control" -> "Active power" to enter the active power interface.
step 2
Set the active control mode to "Scheduling prohibited" and click “Save”.
-- -- E
En
nd
d
10.2.2 Reactive Power
10.2.2.1 Disable
If the grid company does not need the power plant to adjust the voltage at the grid-
connection point, and the inverter does not need to cooperate with the grid for reactive
User Manual