78
figure 7-16
Active Power Regulation
table 7-5 Description of Active Power Regulation Parameters
Parameter
Description
Range
Active Power Soft Start
after Fault
Switch for activating/deactivating the function
of active power soft start after a fault occurs
On/Off
Active Power Soft Start
Time after Fault
The soft start time required for raising active
power from 0 to rated value after a fault occurs
1 s–1200 s
Active Power Gradient
Control
Set whether to enable active power gradient
control
On/Off
Active Power Decline
Gradient
Decline gradient of inverter active power per
minute
1 %/min–
6000 %/min
Active Power Rising
Gradient
Rising gradient of inverter active power per
minute
1 %/min–
6000 %/min
Active Power Setting
Persistence
Switch for activating/deactivating the function
of active power setting persistence
On/Off
Active Power Limit
Switch for limiting active power
On/Off
Active Power Limit
Ratio
The ratio of active power limit to rated power in
percentage
0.0 %–
100.0 %
Reactive Power Regulation
Tap
Settings→Power Regulation Parameters→Reactive Power Regulation
to enter the
screen, as shown in the following figure.
User Manual