2 Electrical Connection
Quick User Manual
14
Main Screen (Press ENT)
→
Menu (Press
×
2)
→
Settings (Press ENT)
→
Input
password 111 (Press ENT)
→
Settings (Press
×10)
→
Existing Sys (Press ENT)
Existing Sys Rated-P:
the rated power of the existing PV
system.
Total Export Limit:
the export power limit of the new
system
The lower limit is the rated power of the existing PV
system.
The upper limit is ([rated power of the hybrid
inverter] + [rated power of the existing PV system]).
For example, retrofit an existing PV system (rated power:
3000 W) with the hybrid inverter SH4K6 (rated power:
4600 W). The total export limit can be set from 3000 W to
7600 W.
The export power limit can also be set via the submenu of Zero-export. Proceed
as follows to perform the settings.
Main Screen (Press ENT)
→
Menu (Press
×
2)
→
Settings (Press ENT)
→
Input
password 111 (Press ENT)
→
Settings (Press
×2)
→
Zero-export (Press ENT)
According to the local regulations in Germany, please set
the export power to 70 % of the installation capacity.
For example, with a total maximum installation capacity of
4600 W (SH4K6), the export power should be set to 3220 W
(i.e. 4600 * 70 %).
The settings in the two submenus are from the same source. If one is
changed, the other will synchronize the value.
Summary of Contents for SH3K6
Page 2: ......
Page 4: ...II System Overview ...
Page 5: ...III ...
Page 6: ...IV ...
Page 7: ...V ...
Page 8: ...VI ...
Page 28: ...3 Commissioning Quick User Manual 18 Fig 3 2 Initial Settings ...