3 Commissioning
19
Zero-export (Partial):
According to the local regulations in Germany, please
set the export power to 70 % of the installation
capacity.
For example, with a total maximum installation
capacity of 4600 W (SH4K6), the export power should
be set to 3220 W (i.e. 4600 * 70 %).
Reactive power regulation:
OFF
:
The reactive power regulation function is disabled.
The power factor (PF) is limited to +1.000.
“
PF
” mode:
The inverter is capable of operating with fixed power factor.
The PF ranges from 0.8 leading to 0.8 lagging.
Leading
: the inverter is sourcing reactive power to the grid.
Lagging
: the inverter is sinking reactive power from the grid.
For the explanations of other modes, see the User Manual in the CD.
Battery parameters:
“No Battery” or “Lead-acid Narada”
option:
“Li-ion Sungrow” option:
“Li-ion LG” option:
Set the battery capacity.