3 Commissioning
Quick User Manual
20
“Li-ion Pylon” option:
“Li-ion GCL” option:
“Li-ion BlueSun” option:
“Li-ion BYD” option:
“Other Lead-acid” option:
Max. Chrg / Max. DChrg
:
Make sure that the charge or discharge current is not beyond
the upper limit (65 A) to protect the battery from overcharging
or deep discharging.
The unit
C
is the “capacity”. If the max charge or discharge is
set to more than 65 A (e.g. C = 600 Ah, 0.3 C = 180 A), then the
inverter will limit the charge and discharge current to 65 A.
If the battery voltage or temperature is beyond the allowable
range, the related error codes will be triggered and the
protection function will be activated to stop charging or
discharging.
DChrgEndVtg
:
Stop discharging at a voltage not lower than DChrgEndVtg, so
as to protect the battery from deep discharging.
The
DChrgEndVtg
setting value should be higher than the
Low Vtg
setting value.