Quick User Manual
3 Commissioning
25
If the battery type or capacity setting is inconsistent with the actual, the
charge/discharge current may be less than the actual charge/discharge ability.
However, the system can operate normally. Proceed as follows to modify.
1.
Stop the inverter via the LCD menu.
Main Screen (Press ENT)
→
Menu (Press
×
1)
→
ON / OFF (Press
ENT)
Confirm your choice by pressing
ENT
.
2.
Reset the battery type and parameters. Proceed as follows to enter the
submenu.
Main Screen (Press ENT)
→
Menu (Press
×
2)
→
Settings (Press
ENT)
→
Input
password 111 (Press
ENT)
→
Settings (Press
×8)
→
Battery Type (Press
ENT)
3.
Start the inverter via the LCD menu.
3.3.3 System Time
The correct system time is very important. If there is deviation between the system
time and the local time, the inverter will not operate normally. The clock is in
24-hour format. Proceed as follows to set the correct time.