Descriptions of the country codes are as follows:
Country Code
Full Name
Language
GB Great
Britain
English
DE Germany German
IT Italy
Italian
AT Austria
German
AU Australia
English
BE Belgium
French
NL Netherlands English
CN China
Chinese
SA South
Africa English
Other
Country not included above
English
5.5
Setting the Protective Parameters
Main Screen (Press ENT)
→
Menu (Press
×
2)
→
Settings (Press ENT)
→
Input
password 111 (Press ENT)
→
Settings (Press
×9)
→
Prot. Param (Press ENT)
When the grid voltage or frequency
reaches the recovery value, the
corresponding fault code displayed on
the LCD will be cleared and the inverter
can start operating.
Power Ramp Rate
: the ramp up/down rate of power variation.
The power rate limit mode is enabled (
ON
) by default.
Set to
OFF
to turn off the function.
The inverter will automatically disconnect from the grid within
3 s when the average voltage for a 10 min period exceeds the
set-point of
10-min Over Vtg
.
Set to
OFF
to turn off the function.
Reconnection time
(Italy only)
:
A reconnection to the network can take place only if the
voltage is between 85 % and 110 % of the nominal value and
the frequency is stably maintained in the range of 49.90
Hz–50.10 Hz.
The reconnection operation will be allowed if the frequency and voltage are stable in
the reconnection time of 300 s if is to be performed with a Gradient positive power not
exceeding 20 % * (maximum power) per minute.