Grid Under-voltage Derating
Export Power Limit Derating
When the meter detects that the export power is greater than the limit value on
the LCD, the inverter will reduce the output power within the specified range.
Power Factor Derating
When the power factor PF<1.0, the inverter will reduce the output power within
a specified range. The following figure shows the power factor derating curve.
P
n
0.8P
n
0.8
1
Power factor
PF derating
Fig. 3-2
Power Factor Derating
3.2.2 External Demand Response
The inverter provides a terminal block for connecting to a demand response
enabling device (DRED). The DRED asserts demand response modes (DRMs).
The inverter detects and initiates a response to all supported demand response
commands within 2s. For the connections, see “
”.
The following table lists the DRMs supported by the inverter.