User Manual
53
4.
Plug the wires into the
corresponding
terminals
according the marks without
tool tightening.
CANH:
blue (pin 4)
CANL:
white-blue (pin 5)
Note:
For reconnection, press the part as
shown in the red circle so as to pull out
the cable.
CANH
CANL
BAT_Com.
5.
Fasten the swivel nut with a torque of 1 N
m–2 N
m and connect the
other end to the battery.
6.8.3 Connecting the Temperature Sensor
When the system is equipped with a lead-acid battery, it is recommended to
connect the PT1000 temperature sensor to the inverter. This is to sample the
battery temperature or the external environment temperature of the battery.
Cable Requirements
Cross-section: 1.0 mm
²
, cable diameter: 3 mm–5.3 mm
Procedure:
1.
Unscrew the swivel nut from
any
Com.
port.
2.
Lead the cable through the
cable gland.