User Manual
58
Inverter inside
Grid
Load
Contactor
DO
Manual
switch
Controlled by
MCU
An AC contactor must be installed between the inverter and
appliances. It is prohibited to connect the load directly to the DO port.
The current of the DO dry contact should not be larger than 3 A.
The DO node is not controlled once the inverter is powered off.
Connect the AC contactor by the manual switch, so as to control the
loads.
Cable Requirements
Cross-section: 1.0 mm
²
, cable diameter: 3 mm–5.3 mm
Procedure:
1.
Unscrew the swivel nut from any
Com.
port.
2.
Lead the cable through the cable
gland.