User Manual
66
Parameter
Description
Range
Over Vtg
The upper limit of battery voltage when
charging
48 V to 70 V
Low Vtg
The lower limit of battery voltage when
discharging
32 V to 48 V
Over Temp
The upper limit of battery temperature
20
℃
to 70
℃
Low Temp
The lower limit of battery temperature
-30
℃
to 10
℃
CSTVtgChar
The voltage of constant-voltage charging.
40 V to 63 V
DChrgEndVtg
The voltage at which the discharging is
stopped
30 V to 53 V
* Consult the battery manufacturer for an advice before any modification.
9.
Check and confirm the communication method. Refer to “
” for the communication configuration.
Use the iSolarCloud APP to create a new plant. For details, refer to the
User Guidance of iSolarCloud APP.
10.
Check the icons on the main screen. Refer to
explanations.
11.
Check the state of the LED indicator.
Tab. 7-5
State Descriptions of the LED Indicator
Color
Status
Description
Green
On
The inverter is running normally.
Blinking
The inverter is in the process of starting.
Off
Other states except Running and Starting.
(Refer to
Red
On
Permanent fault or upgrade failure.
Blinking
Other system faults or main alarms.
Off
No fault occurs.
12.
The running data will be uploaded to the iSolarCloud server
,
visit
or iSolarCloud App to view inverter information.
If the inverter commissioning fails,
Press
to view the current faults. Remove
the existing malfunctions and then repeat starting up the inverter according to
the procedure detailed in this section.
In the case of commissioning failure, power off the system and wait 1
minute to commission the system again.
7.5 Result Verification
Refer to
chapter 3.4
in the quick user manual for details.