User Manual
93
In “Run Info” menu,
Press
/ to
turn to the page showing DRM
information.
Menu
Run Info
ON / OFF
1/2
Settings
DRM State
DRM1
Import Limit
100.0%
Export Limit
100.0%
12.2
Reactive Power Regulation
Only qualified personnel can perform the power regulation settings.
All the parameter settings must comply with standard AS/NZS 4777.
The submenu is as shown on the right.
Refer to “
” for the navigation.
Press
/ to select the desired option and
Press
ENT
to confirm.
For the PF mode, see the reactive power regulation
instruction in “
”.
Reactive Power
PF
OFF
Q(u)
Q(p)
Qt
12.2.1 “Qt” Mode
Qt limit
: the maximum ratio of reactive power to
rated apparent power in %.
The Qt limit ranges from -60.0 % to +60.0 %.
Qt Setting
Qt Limit
+ 060.0%
12.2.2 “Q(P)” Mode
The PF of the inverter output varies in response to
the output power of the inverter.
Leading PF
1.000
Lagging PF
0.900
Upper Power
100.0%
Lower Power
50.0%
Tab. 12-2
“
Q(P)
” Mode Parameter Explanations
Parameter
Explanation
Default
Range
Leading PF
Power factor of the lower power point
1.000
0.900–1.000
Lagging PF
Power factor of the upper power
point
0.900
0.900–1.000
Lower
Power*
Lower limit of the output power (in %)
50 %
0–50 %