2 Electrical Connection
17
Main Screen (Press
ENT
)
→
Menu (Press
×
2)
→
Settings (Press
ENT
)
→
Input
password 111 (Press
ENT
)
→
Settings (Press
×10)
→
Existing Sys (Press
ENT
)
Existing Sys Rated-P:
rated power of the existing
system.
Total Export Limit:
export power upper limit of the
new system
The lower limit is the rated power of the existing PV
system.
The upper limit is ([rated power of the hybrid
inverter] + [rated power of the existing PV system]).
For example, retrofit an existing PV system (rated power: 3000 W) with SH5K hybrid
inverter (rated power: 5000 W). The total export limit can be set from 3000 W to 8000
W.
The export power limit can also be set via the submenu of Zero-export. Proceed as
follows to perform the settings.
Main Screen (Press
ENT
)
→
Menu (Press
×
2)
→
Settings (Press
ENT
)
→
Input
password 111 (Press
ENT
)
→
Settings (Press
×2)
→
Zero-export (Press
ENT
)
The settings in the two submenus are from the same source. If one is
changed, the other will synchronize the value.