Quick User Manual
3 Commissioning
21
Tab. 3-3
Grid Standard Description
Grid company Code
Company
AG AusGrid,
NSW
EE Ergon
Energy,
QLD
EG Energex,
QLD
PN
SA Power Networks,SA
PC Powercor,VIC
WP Western
Power,WA
Default
Company not mentioned above
Tab. 3-4
Parameters of Grid Standards
Parameter
Default
AG
EE
EG
PN
PC
WP
Over-voltage
1-V
max
(V)
260.0
260.0
260.0
260.0
257.0
260.0
260.0
1-Time (s)
2.0
1.80
1.80
1.80
1.80
1.80
1.80
2-V
max
(V)
265.0
265.0
265.0
265.0
265.0
265.0
265.0
2-Time (s)
0.20
0.20
0.20
0.20
0.20
0.20
0.20
Under-voltage
1-V
min
(V)
180.0 200.0 210.0 210.0 200.0 195.0 180.0
1-Time
(s)
2.0
1.80 1.80 1.80 1.80 1.80 1.80
2-V
min
(V)
180.0 200.0 210.0 210.0 200.0 195.0 180.0
2-Time
(s)
2.0
1.80 1.80 1.80 1.80 1.80 1.80
Over-frequency
1-F
max
(Hz)
52.00 52.00 52.00 52.00 52.00 51.50 51.50
1-Time
(s)
0.20 0.20 0.20 0.20 0.20 0.20 0.20
2-F
max
(Hz)
52.00 52.00 52.00 52.00 52.00 51.50 51.50
2-Time
(s)
0.20 0.20 0.20 0.20 0.20 0.20 0.20
Under-frequency
1-F
min
(Hz)
47.00
48.00
47.00
47.00
48.00
48.50
47.00
1-Time (s)
2.0
1.80
1.80
1.80
1.80
1.80
1.80
2-F
min
(Hz) 47.00
48.00
47.00
47.00
48.00
48.50
47.00
2-Time (s)
2.0
1.80
1.80
1.80
1.80
1.80
1.80
10-min voltage
1-V
10-min
(V)
255.0
255.0
255.0
257.0 255.0 255.0 258.0
1-V
10-min
(V)
255.0
255.0
255.0
257.0 255.0 255.0 258.0
* Refer to
Tab. 4-3
for the parameter explanations.
Set the Grid standard for the country code “AU”. Set the protective parameters if
you choose “Manual”.
Summary of Contents for SH5K
Page 1: ...SH5K QUEN Ver14 201708 Version 1 4 Quick User Manual SH5K Grid Connected Hybrid Inverter ...
Page 2: ......
Page 4: ...II System Overview ...
Page 5: ...III ...
Page 6: ...IV ...
Page 7: ...V ...
Page 8: ...VI ...
Page 9: ...VII ...
Page 10: ...VIII ...
Page 32: ...3 Commissioning Quick User Manual 20 Fig 3 2 Initial Settings ...