4 Operation
Quick User Manual
34
The inverter will automatically disconnect from the grid within
3 s when the average voltage for a 10 min period exceeds the
set-point of
10 Min Over Vtg
.
The protective function is enabled by default with the default
set-point of 255.0 V and lies in range 244 V–258 V.
4.6
Setting the Communication Parameters
Main Screen (Press
ENT
)
→
Menu (Press
×
2)
→
Settings (Press
ENT
)
→
Input
password 111 (Press
ENT
)
→
Settings (Press ×7)
→
Comm. Param (Press
ENT
)
The communication address ranges
from 1 to 247.
The IP, sub net, gateway, DNS1 and
DNS2 can be modified only when
the DHCP is set to OFF.
Acquire the IP, subnet mask,
gateway, DNS1 and DNS2 from the
network professional.
Summary of Contents for SH5K
Page 1: ...SH5K QUEN Ver14 201708 Version 1 4 Quick User Manual SH5K Grid Connected Hybrid Inverter ...
Page 2: ......
Page 4: ...II System Overview ...
Page 5: ...III ...
Page 6: ...IV ...
Page 7: ...V ...
Page 8: ...VI ...
Page 9: ...VII ...
Page 10: ...VIII ...
Page 32: ...3 Commissioning Quick User Manual 20 Fig 3 2 Initial Settings ...