1.5.3. Anti-stagnation
The anti-stagnation function is designed to protect the solar fluid and collector during times of
high solar radiation.
x
If the collector circuit sensor (
T1
on single collector systems,
T1
&
T4
on east-west
collector systems) registers over the
Anti-stagnation Start
temperature on the
Settings
menu, the designated valve or pump is activated.
x
When the collector circuit has cooled down to below the
Anti-stagnation stop
temperature (
Settings
menu) the valve or pump will deactivate.
x
See
Settings
menu/
Extra Functions
/
Anti-stagnation
for further information.
This function is available only if selected on the Extra Menu
P1
T2
T1
P3
T3
P1
T2
T1
P3
T3
The anti-stagnation function can be used to direct excess heat
from the system into a designated heat dump, i.e., fan coil,
ground loop, or hot tub/pool.