22
¤¤
Service
---------- - -
Energy Measurement
Pump P1
PhAC SC
Pump P2
No SC
Glycol
DowFrost HD
Glycol Mix
50%
Factory setting
no
£
Reset op time no %
C
¤¤
Service
---------- - -
Pump P1
PhAC SC
Pump P2
No SC
Glycol
DowFrost HD
Glycol Mix
50%
Factory setting
no
Reset op time
no
£
Time graf temp 5m
m
C
¤¤
Service
---------- - -
Pump P2
No SC
Glycol
DowFrost HD
Glycol Mix
50%
Factory setting
no
Reset op time
no
Time graf temp
5m
£
Time graf op 1h
m
C
¤¤
Service
---------- - -
Glycol
DowFrost HD
Glycol Mix
50%
Factory setting
no
Reset op time
no
Time graf temp
5m
Time graf op
1h
£
Calib sensors
m
C
1.15. Reset op time:
To reset the all of the operation hours to zero:
x
Press
(>)
to highlight the line.
x
Select “
yes
” with
(+)
key.
x
Press
(<)
repeatedly to return to the main menu.
Caution: This will erase all previously recorded data (Power, Energy, temperature )
1.16. Time graph temp:
Adjusts the graphical scale for the Temp vs. Time graphs (adjustable from 1 to 60 minutes).
1.17. Time graph op:
Adjusts the graphical scale for the
Operation h menu
vs. time graphs (adjusts from 1 to 48
hours).
1.18. Calibration of sensors:
CAUTION:
Check the temperature with a calibrated thermometer before adjusting.
(Calibration range is from -6°F to +5°F with factory default setting of 0°F)
See
Temperature
(section 5)
for
more detailed
information.
See
Operation h
(section 4)
for
detailed
information.
On this submenu
you can calibrate all
the temperature
sensors connected
to your system.