28
2.15. Cooling Function:
2.15.1. Cooling start:
When the water temperature in the top of the system tank (
T3
) rises above this setting,
P3
will activate to start cooling the tank by transferring water to the external tank or heat sink.
(Adjustable from 68°F to 194°F with factory default set at 104°F)
2.15.2. Cooling hyst:
When the water temperature at the top of the system tank (
T3
) falls under the
Start
temperature (see
2.15.1
above) minus the
Hysteresis
setting,
P3
will disengage.
(Adjustable from 3°F to 54°F with factory default set at 18°F)
¤¤
Service
--------- - --- --
English
Time and date
US Version
yes
System
Extra
off
£
Extra cooling
--
Protection func.
¤¤
Settings
--------------
dT Max tank1
49°F
dT Min tank1
38°F
Min rev pump
50%
dTFS
59°F
Mintemp coll.
32°F
Cooling
£
Start
104°F
¤¤
Settings
--------------
dT Min tank1
38°F
Min rev pump
50%
dTFS
59°F
Mintemp coll.
32°F
Cooling
Start
104°F
£
Hysteresis
18°F
Water temperature on top of tank1 T3 (°F)
Cooling stop
(start – hysteresis)
Cooling start
P3