4.1 TMIN S (X)
Enable/start temperature at sensor X:
If this value is exceeded at the applicable sensor X and the other conditions are also met, then the controller switches on the associated pump and/
or valve. If the temperature at the sensor drops below this value by 5°C, then the pump and/or the valve are switched off again.
Settings range : 0°C to 99 °C (32°F to 210 °F / Default setting: 20°C (68°F)
4.2 TMAX S (X)
Switch-off temperature at sensor X
If this value is exceeded at the applicable sensor X, the controller switches the associated pump and/or valve off. If the temperature falls below this
value again and the other conditions are also met, then the controller switches the pump and/or valve on again.
Settings range : 0°C to 99 °C (32°F to 210 °F) / Default setting: 60°C (140°F)
DANGER
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided by
the customer!
4.3 TMAX SB
Switch-off temperature at pool sensor
If this value is exceeded at the applicable sensor, the controller switches the associated pump and/or valve off. If the temperature falls below this
value again and the other conditions are also met, then the controller switches the pump and/or valve on again.
Settings range : 0°C to 50 °C (32°F to 122°F / Default setting: 30°C (86°F)
DANGER
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided by
the customer!
4.4 TMAX SB WT
Switch-off temperature at heat exchanger sensor
If this value is exceeded at the applicable sensor, the controller switches the associated pump and/or valve off. If the temperature falls below this
value again and the other conditions are also met, then the controller switches the pump and/or valve on again.
Settings range: 0°C to 50°C (32°F to 122°F) / Default setting: 28°C (82°F)
DANGER
Temperature values that are set too high can lead to scalding or damage to the system. Scalding protection must be provided by
the customer!