RELA
Y FUNC
TIONS
The relay is switched on at the same time as the set relay R1 or R2.
Settings range: On, Off, Inverted
This menu determines how long after the start of R1 or R2 the parallel relay is switched on.
Settings range: 0-120 seconds / Default setting: 30 seconds
6.4.14 Parallel Operation (X)
6.4.14.1 Delay
This menu determines how long after the switch off of R1 or R2 the parallel relay is switched off.
Settings range: 0-120 seconds / Default setting: 30 seconds
6.4.14.2 Followup Time
Relay is always switched on.
6.4.15 Always On
Heat circuit pump is controlled with a fixed hysteresis of (+/-1° for setpoint temperature). 30 seconds Switch on and Switch off delay is fixed set-
ting to prevent unnecessary switching of the pump.
RC21 room controller can be used as room temperature sensor.
Settings range: On, Off
Room reference temperature in day mode. If this temperature is exceeded at the room temperature sensor at the set times, the relay is switched
off.
Settings range: 10°C to 30°C (50°F to 86°F)
6.4.16 Heating Circuit
6.4.16.1 Room Set Day
Room reference temperature in night mode. If this temperature is exceeded at the room temperature sensor at the set times, the relay is
switched off.
Settings range: 10°C to 30°C (50°F to 86°F)
6.4.16.2 Room Set Night