J.7 0-10V ON
This voltage is needed to turn the pump on at minimum speed.
Settings range: (Solar:) 0.0 to 5.0 V / Default setting: 1.0 V - (Heating:) 5.0 to 10.0 V / Default setting: 9.0 V
J.8 0-10V MAX
This determines the output voltage for the highest speed of the pump, that is used e.g. during purging or manual operation
Settings range: (Solar:) 5.0 to 10.0 V / Default setting: 10.0 V - (Heating:) 0.0 to 5.0 V / Default setting: 0.0 V
J.9 SPEED WHEN “ON”
This menu determines the calculated and displayed speed of the pump. If e.g. 30% is set here and the signal set in “PWM on/0-10V on” is put out,
30% speed is displayed. When the signal set in “PWM max/0- 10V max” is put out, 100% speed is displayed. Everything in between is calculated
accordingly.
Settings range: 10 to 90 % / Default setting: 30 %
CAUTION
This function has no influence on the regulation, but changes only the speed displayed.
J.10 SHOW SIGNAL
Displays the set signal in text and a graphical diagram.
Example For Pump Settings: