SunMaxx Solar | 5098 NY 206 Bainbridge NY 13733 | 1.877.786.6299 1.877.270.7875 fax | www.sunmaxxsolar.com
B.1 SPECIFICATIONS
B. Description Of Controller
Electrical Specifications
Mains Voltage
100 - 240VAC
Mains Frequency
50 - 60 Hz
Power Consumption
0.5W - 2.5W
Internal Fuse
T2A / 250V slow blow
Protection Category
IP40
Protection Class
II
Overvoltage Category
II
Degree of Pollution Category
II
Network Connections
CAN Bus
Permissible Cable Length Of Sensors & Appliances:
Collector and outdoor sensor
< 98 ft
Other PT1000 Sensors
< 32 ft
VFS / RPS Sensors
< 10 ft
CAN
< 10 ft
PWM / 0...10V
< 10 ft
Electronic Relay
< 10 ft
Mechanical Relay
< 32 ft
Real Time Clock
RTC w/ 24 Hour Power Reserve
Permissible Ambient Conditons:
Ambient Temperature
For Controller Operation
32
0
F to 104
0
F
For Transport / Storage
32
0
F to 140
0
F
Air Humidity
For Controller Operation
Max: 85% rel. humidity @ 77
0
F
For Transport / Storage
no moisture condensation
Other Specifications & Dimensions:
Housing Design
3-Part, ABS Plastic
Installation Methods
Wall Install / Optional Panel Install
Overall Dimensions
6.42” x 4.33” x 2.05”
Aperture Installation Dimensions
6.18” x 4.33” x 2.05”
Display
Full graphical display, 128 x 128
Light Diode
Multi-color, Red / Green
Operation
4 entry keys
vers. 1
Vers. 2
Vers. 3
Vers. 4
Mechanical relay 460VAC for AC1 / 460W for AC3
3 (R1 - R3)
2 (R2 - R3)
3 (R1 - R3)
1 (R3)
Electronic relay: min. 5W / max. 120W for AC3
-
1 (R1)
-
2 (R1 - R2)
0-10V output, tolerance 10%, 10 k Ω load or
PWM output freq. 1 kHz, level 10 V
1
1
2
2
PT1000 aensor input measuring range -40C to 300C
5
5
6
6
VFS / RPS inputs
0C to -100C (-25C to 120C short term)
-
-
2
2
0.26 G/min. - 3.17 G/min. (VFS 1 - 12)
0.53 G/min. - 10.57 G/min. (VFS 2 - 40)
1.32 G/min. - 26.42 G/min. (VFS 5 - 100)
2.64 G/min. - 52.83 G/min. (VFS 10 - 200)
0 - 0.6 bar
0 - 1 bar
0 - 1.6 bar
0 - 2.5 bar
0 - 4 bar
0 - 6 bar
0 - 10 bar