In Energy savings mode, different settings may apply, see e.g. T eco.
DANGER
Temperature values which are set too high can lead to scalding or damage to the system. Scalding protection must be provided
by the customer!
6.4.1 TH Set
Taget temperature at thermostat sensor 1. Below this temperature, additional heating is switched on, till TH set + hysteresis is reached.
Settings range: -20 bis 99°C / Default setting: 50
6.4.2 TH Hysteresis
Hysteresis of setpoint temperature.
Settings range: 1 bis 50°C / Default setting: 10K
6.4.3 Thermostat Sensor 1
T set is measured with thermostat sensor 1.
When thermostat sensor 2 is connected, the relay switches on when T set is undershot at thermostat Sensor 1, and switches off when T set +
hysteresis at thermostat sensor 2 is exceeded.
Settings range: S1-S8, VFS1-2, active storage / Default setting: none
6.4.4 Thermostat Sensor 2
Optional switch off sensor
When T set + hysteresis is exceeded at the optional thermostat sensor 2, the relay is switched off.
Settings range: S1-S8, VFS1-2, active storage / Default setting: none
6.4.5 T eco
For Energy saving mode
When Energy saving mode is active: During solar charge T eco is used instead of TH set. When the temperature drops below T eco at thermostat
sensor 1, the relay is switched on and heats up to T eco + hysteresis.
Settings range: 0-99°C / Default setting: 40°C
6.4.6 Storage
For Energy saving mode
Loading this storage activates the Energy saving mode When this storage is charge by solar, additional heating is only switched on when the
temperature is below T eco.
Settings range: (Storage sensors) / Default setting: fi rst storage
6.4.7 Energy Saving Mode
Energy saving mode switches the heating on when T eco is undershot und heats up to T eco + hysteresis when solar charge is active.
Settings range: On, Off / Default setting: Off