6.4.8 Periods
Thermostat activity times
Set the desired periods of time when the thermostat should be active. 3 periods can be set per day, settings can also be copied to other days.
Outside the set times the thermostat is switched off.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
6.5 COOLING
This is used to cool down e.g. storages to a setpoint temperature by radiating heat.
Settings range: S1-S8, VFS1-2, active Storage / Default setting: None
6.5.1 Co T Set
Target temperature at thermostat sensor 1. Cooling is on above this temperature till Co T set + hysteresis is reached.
Settings range: 0°C to 99°C (32°F to 210°F) / Default setting: 50°C (122°F)
6.5.2 Co Hysteresis
If the temperature at th drops below Co T set + hysteresis, the relay is switched off.
Settings range: -50 bis -1 / Default setting: -10
6.5.3 Cooling (Sensor)
Reference sensor of the cooling function.
Settings range: (Storage sensor) / Default setting: First storage
6.5.4 Periods
Cooling activity times
Set the desired periods of time when the cooling should be active. 3 periods can be set per day, settings can also be copied to other days. Outside
the set times the cooling function is switched off.
Setting range: from 00:00 to 23:59 /default setting: 06:00 to 22:00
6.6 RETURN FLOW INCREASE
This function is used to raise the temperature of e.g. the return fl ow by the storage.
Settings range: On, Off
6.6.1 RF Tmax
Maximum temperature at the storage sensor. If this temperature is exceeded, the relay is switched off.
Settings range: 0°C to 99°C (32°F to 210°F) / Default setting: 70°C (158°F)